2008-07-08 13:31:41 | ** DENIED2ND REVIEW ** |
| |
| ** PLEASE KNOW THERE ARE SOME ITEMS FROM PREVIOUS |
| REVIEW IN NEED OF ADDRESSING. |
| |
| ** PLEASE SEE THERE ARE SOME NEW ITEMS FROM THIS REVIEW |
| WHICH ARE NEW BASED ON REVISED PLANS AND DOCUMENTS SUCH |
| AS ENERGY CALCULATIONS ONLY NOW BEING SUBMITTED FOR THE |
| FIRST TIME. |
| |
| 1) NOTE: PLEASE REVISED AND VERIFY CODE LISTED ON E-3. |
| PLANS SHOULD READ FBC 2004 W/ 2007 REVISIONS HOWEVER |
| PLANS SHOW FBC 2004/2007. THIS COULD MISLEAD TO AN |
| UNDERSTANDING THAT THE 2007 FBC MAY BE USED OR IS PART |
| OF THE DESIGN. |
| PLEASE REVISE. IF THIS WERE THE ONLY ITEMS PLANS COULD |
| HAVE BEEN REDLINED. |
| |
| 2) NOTE: PLEASE SEE ELECTRICAL NOTES ADDED TO SHEET E-1 |
| STATES LIGHTING CONTROLS TO BE INSTALLED HOWEVER PLANS |
| DO NOT SHOW ANY LIGHTING CONTROLS. MAY NOT QUOTE THE |
| CODE IN LIEU OF DESIGN. |
| PLEASE CALL TO GO OVER LIGHTING CONTROLS FOR AREAS |
| WHICH ARE REQUIRED. SQ FT IS NOW BEING SHOWN LESS THAN |
| 5K SQ FT HOWEVER THERE ARE SOME AREAS WHICH STILL |
| REQUIRE AUTOMATED CONTROLS. |
| 13-415.1.ABC.1.1, .1.2, .1.3. |
| |
| ** THE INPUT DATA REPORT SHOWS OCCUPANCY SENSORS AS THE |
| METHOD OF CONTROLS. |
| |
| 3) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| ALONG WITH THE INPUT DATA REPORT WHICH IS PART OF THE |
| CALCULATIONS DO NOT COORDINATE WITH THE PLANS |
| SUBMITTED. THE INPUT DATA REPORT WILL BE NOTED AS IDR |
| IN THE REMAINDER OF THIS COMMENT. THERE WILL BE SEVERAL |
| EXAMPLES GIVEN AS A BENEFIT HOWEVER THESE EXAMPLES ARE |
| NOT AN EXHAUSTED LIST OF ALL POSSIBLE ITEMS. |
| ** PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2 AND |
| .1.3. |
| PLEASE KEEP IN MIND THE FIXTURE WATTAGE IS REQUIRED TO |
| BE USED NOT THE BULB WATTAGE. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE LIGHTING SHOWN ON THE IDR FOR EXTERIOR |
| LIGHTING. PLANS SHOW AS MANY AS 6 75WATT EXTERIOR |
| FIXTURES YET THE IDR SHOW ONLY 4. |
| |
| FOR EXAMPLE: |
| THE IDR DOES NOT SHOW ANY OF THE 175W FIXTURES AS SHOWN |
| ON PLANS FOR FLOODS YET THE PLANS SHOW AS MANY AS 8 TWO |
| HEADED FLOODS. |
| |
| FOR EXAMPLE: |
| THERE IS HOT WATER PIPING IN BUILDING YET THE IDR IS |
| BLANK. (NOTED FOR OTHER TRADES AS FYI) |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE IDR FOR THE AMOUNT OF DOORS FROM |
| CONDITIONED SPACE TO UNCONDITIONED SPACE. ( NOTED FOR |
| OTHER TRADES AS FYI) |
| |
| FOR EXAMPLE: |
| PLEASE TAKE A LOOK AT THE SQUARE FOOTAGE SHOWN FOR |
| CONDITIONED AND UNCONDITIONED SPACE. THE SUBMITTED |
| ENERGY CALCULATIONS INDICATE A TOTAL OF 1986 SQ FT YET |
| THE PLANS SHOW OVER 4K SQ FT. |
| PLEASE CORRELATE ALL. |
| |
| FOR EXAMPLE: |
| PLEASE SEE THE INTERIOR LIGHTING AS ONLY SOME OF THE |
| 128W FIXTURES ARE SHOWN IN THE IDR. IN FACT ONLY 6 OF |
| THESE FIXTURES ARE SHOWN WHEN THE PLANS SHOW MORE THAN |
| TWO DOZEN. |
| |
| |
| ** THE ABOVE ARE SOME EXAMPLES. |
| |
| 4) NOTE: PLEASE COORDINATE THE PANELS ON THE RISER WITH |
| THE PANELS ON THE PANEL SCHEDULE. THE PANELS ARE BEING |
| SHOWN AS 100AMPS ON RISER AND 200AMPS ON SCHEDULES. |
| 408, 310, |
| FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |