Plan Review Notes
Plan Review Notes For Permit 08020693
Permit Number 08020693
Review Stop P
Sequence Number 1
Notes
Date Text
2008-03-29 10:12:58DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 A. FIRST REVIEW UNDER THIS PERMIT NUMBER. PREVIOUS
 REVIEW WAS DONE UNDER APPLIED NUMBER 07030453 WHICH HAS
 EXPIRED.
  
 1. SHT A4 ROOF DRAINAGE CALCULATIONS DO NOT APPEAR TO
 INCLUDE THE VERTICAL CONTRIBUTION OF THE PARAPET WALLS.
 PLEASE INDICATE THE HEIGHT OF THE PARAPET WALLS. ALSO
 SHOW THE HEIGHT OF THE ROOF AT BOTH THE HIGH END AND
 THE LOW END TO VERIFY VERTICAL CONTRIBUTION. SECTIONS
 1101.1, 1106 & 1107.--SECONDARY DRAINAGE IS
 REQUIRED PER SECTION 1107.1. PLEASE SHOW THE LOCATION
 OF ALL SECONDARY ROOF DRAINAGE, (EMERGENCY OVERFLOW
 SCUPPERS PER SECTION 1503.4.3).--GUTTERS WITH
 DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF
 LESS THAN 6 INCHES HORIZONATL PROJECTION EXCEPT FOR
 GABLE END RAKES OR ON A ROOF ABOVE ANOTHER ROOF. A
 COLLECTOR HEAD AT THE TOP OF THE DOWNSPOUT WILL BE
 APPROVED IN PLACE OF THE GUTTER. SECTION 1503.6. (SHOW
 THE DISCHARGE OF THE DOWNSPOUT A MINIMUM 1FT FROM
 STRUCTURE SIDEWALL). SUBMIT A DETAIL FOR THE COLLECTOR
 HEAD SHOWING LENGTH, WIDTH & HEIGHT. ALSO INDICATE THE
 SIZE OF THE DOWNSPOUTS.
  
 2.DRINKING FOUNTAINS ARE REQUIRED IN ALL OCCUPANCIES.
 SERVICE SINKS ARE REQUIRED IN F2 OCCUPANCIES AND IN THE
 STORAGE OCCUPANCY. TABLE 403.1. PLEASE SHOW THE
 REQUIRED FIXTURES ON THE FLOOR PLAN, SANITARY & WATER
 RISER DIAGRAMS.
  
 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAINS SHOWING
 COMPLIANCE WITH SECTION 11-4.15 WITH ALL SUBSECTIONS AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 4. SUBMIT DETAILS FOR ALL TOILET ROOMS SHOWING
 COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19 & 11.4-22
 WITH ALL SUBSECTIONS. THE LAV SHALL BE A MINIMUM 15"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE TO CENTER
 ON THE 30" WIDTH OF THE 30"X48" CLEAR FLOOR SPACE.
  
 5. THE BATHROOM SHALL BE ACCESSIBLE. SUBMIT DETAILS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.19,
 11-4.21 & 11-4.22 WITH ALL SUBSECTIONS. THE SPACING FOR
 THE WATER CLOSET IS A MINIMUM 33". SHOW THE W/C 18" OFF
 ONE FIXTURE AND 15" OF THE OTHER FIXTURE TO SHOW
 COMPLIANCE.
  
 6. SHT A.2 THE BREAK ROOM SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 WITH ALL SUBSECTIONS. A TURNING AREA IN THE
 BREAK ROOM IS REQUIRED PER SECTION 11-4.2.3. PLEASE
 SHOW ON FLOOR PLAN ALONG WITH THE CLEAR FLOOR SPACE.
 FORWARD APPROACH REQUIRED. CABINET DOORS ARE NOT
 ALLOWED IN THE CLEAR FLOOR SPACE.
  
 7. SHT MP3 WATER HEATER DETAIL. THERMAL EXPANSION
 CONTROL IS REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD ON DETAIL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved