2008-03-20 17:17:22PLAN DENIED
 PAGE A4 ON PLANS SHOW ROOF TOP UNIT DETAIL, R19
 INSULATION SEE SECTION 13.406.1ABC.1.4 FLORIDA ENERGY
 CODE .
 PAGE A 4 ON ROOR TOP UNIT DETAIL PLEASE SHOW CURB TO
 ROOF TIEDOWN AND UNIT TO CURB TIEDOWN .
 PAGE MP1 PLEASE PROVIDE RETURN AIR GRILL SIZE IN OFFICE
 1,3 AND RECIPITION AREA.
 PLEASE PROVIDE SUPLY TRUNK LINE SIZE AND RETURN AIR
 TRUNKLINE SIZE ON THE PLANS
 PLEASE REFER TO SECTION 606 AND 606.4.1 FBC(M) 2004