Plan Review Notes For Permit 08020693 |
Permit Number |
08020693 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-20 17:17:22 | PLAN DENIED | | PAGE A4 ON PLANS SHOW ROOF TOP UNIT DETAIL, R19 | | INSULATION SEE SECTION 13.406.1ABC.1.4 FLORIDA ENERGY | | CODE . | | PAGE A 4 ON ROOR TOP UNIT DETAIL PLEASE SHOW CURB TO | | ROOF TIEDOWN AND UNIT TO CURB TIEDOWN . | | PAGE MP1 PLEASE PROVIDE RETURN AIR GRILL SIZE IN OFFICE | | 1,3 AND RECIPITION AREA. | | PLEASE PROVIDE SUPLY TRUNK LINE SIZE AND RETURN AIR | | TRUNKLINE SIZE ON THE PLANS | | PLEASE REFER TO SECTION 606 AND 606.4.1 FBC(M) 2004 | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|