Date |
Text |
2008-03-11 12:59:34 | ** DENIED** |
| |
| FIRST REVIEW UNDER NEW PERMIT APPLICATION FOR THIS |
| ADDRESS. |
| PREVIOUS REVIEW WAS DONE UNDER APPLIED # 07030453 WHICH |
| HAS NOW EXPIRED. |
| |
| |
| |
| 1) NOTE:PLEASE SEE THE FOLLOWING CODES SHALL BE |
| STATED ON PLANS. NEEDS TO BE ON ELECTRICAL PLANS AS |
| WELL AS COVER SHEET. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 (PLANS SHOW 2004) |
| |
| 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUESTED |
| ON PREVIOUS REVIEW. AS THESE WERE NOT SUBMITTED NO |
| REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME. |
| PLEASE SEE 13-101.1.2, 13-400.3.B, 13-400.3.C, |
| 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| |
| 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 AND .1.4 FOR |
| MISSING LIGHTING CONTROLS. |
| PLEASE BE SURE TO SEE AUTOMATED CONTROLS REQUIRED IN |
| .1.2 FOR INTERIOR LOCATIONS AS NOTED IN THE CODE. |
| PLEASE BE SURE TO PROVIDE THE INFORMATION FOR EXTERIOR |
| CONTROLS AS REQUIRED IN .1.4 AS NOTED ABOVE. |
| |
| 4) NOTE: PLEASE SEE E-2 AS THIS WAS PRINTED AND MUCH OF |
| THE INFORMATION ON PANEL SCHEDULE FOR LOADS, CIRCUITING |
| ETC IS BLURRY AND NOT EASILY READ. |
| PLEASE REPRINT WITH MORE CLARITY. |
| FBC 106.1 |
| |
| 5) NOTE: PLEASE SEE SERVICE RISER ONLY SHOWS ONE RISER |
| AND ONLY ONE SET OF CONDUCTORS. THERE IS PART OF THE |
| CONDUCTORS WHICH NOTES *EACH* HOWEVER NO INFORMATION ON |
| IF THERE ARE PARALLEL RISERS. |
| PLEASE SHOW FOR PARALLEL CONDITIONS AS REQUIRED. |
| 240.4, 310.16 |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE IS NOTED TO |
| STRUCTURAL STEEL HOWEVER IS ALSO REQUIRED TO FOOTER |
| STEEL PER 250.50 |
| |
| 7) NOTE: PLEASE SEE RISER IS MISSING ANY METERING |
| DEVICE? METER CAN, CT ETC. |
| PLEASE CONTACT FPL FOR SERVICE REQUIREMENTS AND SEE FPL |
| MINIMUM SERVICE SPECIFICATIONS. THIS INFORMATION CAN BE |
| FOUND AT FPL WEBSITE. |
| HTTP://WWW.FPL.COM/DOINGBUSINESS/BUILDER/B1_INDEX.SHTML |
| |
| |
| 8) NOTE: PLEASE PROVIDE THE ACTUAL AIC RATING OF THE |
| EQUIPMENT. THE PLANS INDICATE THE AVAILABLE FAULT |
| CURRENT AT SERVICE ETC HOWEVER DOES NOT PROVIDE RATINGS |
| ON EQUIPMENT. |
| 110.9, 110.3, 90.7 |
| FBC 106.1.2 |
| |
| 9) NOTE: PLEASE PLACE THE REQUIRED DISCONNECTS FOR ANY |
| ROOF-TOP A/C EQUIPMENT ON ELECTRICAL PLANS. |
| 440.11 |
| |
| 10) NOTE: PLEASE SEE 210.63 AND 210.8B FOR GFI REQUIRED |
| FOR ANY ROOF-TOP AC EQUIPMENT. |
| |
| 11) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL |
| FIXTURES ON PLANS. |
| PLEASE BE SURE TO SEE NOTE #2 FOR COORDINATION WITH THE |
| ENERGY CALCULATIONS TO BE SUBMITTED. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. |
| |
| 12) NOTE: PLEASE SEE SEVERAL NOTES ON E-3 STATES THERE |
| MAY BE SOME SORT OF FIRE ALARM SYSTEM HOWEVER NO SYSTEM |
| COULD BE LOCATED ON PLANS. |
| THERE ARE ALSO NOTES WHICH STATES THE HORN AND STROBE |
| LEVELS SHALL MEET NFPA-72, HOWEVER PLEASE SEE FBC |
| 11?4.28.1, .2 AND .3(4) FOR MINIMUM LOCATIONS AND |
| LEVELS FOR FBC ADA. |
| |
| 13) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET |
| NEC 220. |
| PLEASE SEE PANEL *A* FOR EXAMPLE*: HOW ARE THE |
| APPLIANCE LOADS BEING FIGURED? |
| PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC. |
| CONTINUOUSLOADS WERE SHOWN AT 125%. |
| |
| 14) NOTE: PLEASE SEE THE PLANS NEED TO IDENTIFY THE |
| LOCATION OF PANEL *A* AS AN ELECTRICAL ROOM. THIS MAY |
| NOT BE A CLOSET. |
| SIGNAGE WILL ALSO BE REQUIRED. |
| 110.26, 240.24, 408.17 ETC |
| FBC 106.1.2 |
| |
| *** AS NOTED, AS THERE SOME ITEMS NOT YET SUBMITTED A |
| FULL AND COMPLETE REVIEW CAN NOT BE DONE.PLEASE KNOW |
| THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS |
| TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |