Plan Review Notes
Plan Review Notes For Permit 08020693
Permit Number 08020693
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-11 12:59:34** DENIED**
  
 FIRST REVIEW UNDER NEW PERMIT APPLICATION FOR THIS
 ADDRESS.
 PREVIOUS REVIEW WAS DONE UNDER APPLIED # 07030453 WHICH
 HAS NOW EXPIRED.
  
  
  
 1) NOTE:PLEASE SEE THE FOLLOWING CODES SHALL BE
 STATED ON PLANS. NEEDS TO BE ON ELECTRICAL PLANS AS
 WELL AS COVER SHEET.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (PLANS SHOW 2004)
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS AS REQUESTED
 ON PREVIOUS REVIEW. AS THESE WERE NOT SUBMITTED NO
 REVIEW OF THESE ITEMS COULD BE DONE AT THIS TIME.
 PLEASE SEE 13-101.1.2, 13-400.3.B, 13-400.3.C,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SEE 13-415.1.ABC.1.2 AND .1.4 FOR
 MISSING LIGHTING CONTROLS.
 PLEASE BE SURE TO SEE AUTOMATED CONTROLS REQUIRED IN
 .1.2 FOR INTERIOR LOCATIONS AS NOTED IN THE CODE.
 PLEASE BE SURE TO PROVIDE THE INFORMATION FOR EXTERIOR
 CONTROLS AS REQUIRED IN .1.4 AS NOTED ABOVE.
  
 4) NOTE: PLEASE SEE E-2 AS THIS WAS PRINTED AND MUCH OF
 THE INFORMATION ON PANEL SCHEDULE FOR LOADS, CIRCUITING
 ETC IS BLURRY AND NOT EASILY READ.
 PLEASE REPRINT WITH MORE CLARITY.
 FBC 106.1
  
 5) NOTE: PLEASE SEE SERVICE RISER ONLY SHOWS ONE RISER
 AND ONLY ONE SET OF CONDUCTORS. THERE IS PART OF THE
 CONDUCTORS WHICH NOTES *EACH* HOWEVER NO INFORMATION ON
 IF THERE ARE PARALLEL RISERS.
 PLEASE SHOW FOR PARALLEL CONDITIONS AS REQUIRED.
 240.4, 310.16
 FBC 106.3.5.1.2, 106.1.2
  
 6) NOTE: PLEASE SEE THE GROUNDING ELECTRODE IS NOTED TO
 STRUCTURAL STEEL HOWEVER IS ALSO REQUIRED TO FOOTER
 STEEL PER 250.50
  
 7) NOTE: PLEASE SEE RISER IS MISSING ANY METERING
 DEVICE? METER CAN, CT ETC.
 PLEASE CONTACT FPL FOR SERVICE REQUIREMENTS AND SEE FPL
 MINIMUM SERVICE SPECIFICATIONS. THIS INFORMATION CAN BE
 FOUND AT FPL WEBSITE.
 HTTP://WWW.FPL.COM/DOINGBUSINESS/BUILDER/B1_INDEX.SHTML
  
  
 8) NOTE: PLEASE PROVIDE THE ACTUAL AIC RATING OF THE
 EQUIPMENT. THE PLANS INDICATE THE AVAILABLE FAULT
 CURRENT AT SERVICE ETC HOWEVER DOES NOT PROVIDE RATINGS
 ON EQUIPMENT.
 110.9, 110.3, 90.7
 FBC 106.1.2
  
 9) NOTE: PLEASE PLACE THE REQUIRED DISCONNECTS FOR ANY
 ROOF-TOP A/C EQUIPMENT ON ELECTRICAL PLANS.
 440.11
  
 10) NOTE: PLEASE SEE 210.63 AND 210.8B FOR GFI REQUIRED
 FOR ANY ROOF-TOP AC EQUIPMENT.
  
 11) NOTE: PLEASE COMPLETE THE FIXTURE LEGEND WITH ALL
 FIXTURES ON PLANS.
 PLEASE BE SURE TO SEE NOTE #2 FOR COORDINATION WITH THE
 ENERGY CALCULATIONS TO BE SUBMITTED.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 12) NOTE: PLEASE SEE SEVERAL NOTES ON E-3 STATES THERE
 MAY BE SOME SORT OF FIRE ALARM SYSTEM HOWEVER NO SYSTEM
 COULD BE LOCATED ON PLANS.
 THERE ARE ALSO NOTES WHICH STATES THE HORN AND STROBE
 LEVELS SHALL MEET NFPA-72, HOWEVER PLEASE SEE FBC
 11?4.28.1, .2 AND .3(4) FOR MINIMUM LOCATIONS AND
 LEVELS FOR FBC ADA.
  
 13) NOTE: PLEASE SEE THE LOAD CALCULATIONS NEED TO MEET
 NEC 220.
 PLEASE SEE PANEL *A* FOR EXAMPLE*: HOW ARE THE
 APPLIANCE LOADS BEING FIGURED?
 PLEASE SEE 220.12, 220.14, 220.42, 220.44 ETC.
 CONTINUOUSLOADS WERE SHOWN AT 125%.
  
 14) NOTE: PLEASE SEE THE PLANS NEED TO IDENTIFY THE
 LOCATION OF PANEL *A* AS AN ELECTRICAL ROOM. THIS MAY
 NOT BE A CLOSET.
 SIGNAGE WILL ALSO BE REQUIRED.
 110.26, 240.24, 408.17 ETC
 FBC 106.1.2
  
 *** AS NOTED, AS THERE SOME ITEMS NOT YET SUBMITTED A
 FULL AND COMPLETE REVIEW CAN NOT BE DONE.PLEASE KNOW
 THERE MAY BE COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II