2008-03-21 18:52:15 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)WHEN RESUBMITTING, ALL CHANGES TO THE PLAN ARE TO |
| BE CLOUDED AND INDICATED WITH REVISION MARKERS, REMOVE |
| AND REPLACE REVISED SHEETS AS NECESSARY.INCLUDE A |
| RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| ADDRESSED. |
| |
| 2.)IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY |
| PRIOR TO PERMIT ISSUANCE, 2300 N JOG RD.PLEASE CALL |
| 561-233-5025 FOR MORE INFORMATION.THE PLANS MUST BE |
| STAMPED AND THE RECEIPT IS TO BE INCLUDED WITH THE |
| PERMIT APPLICATION. |
| |
| 3.)PLEASE PROVIDE A BREAKDOWN OF COST FOR THE |
| RENOVATION AREA AND NEW AREAS. |
| |
| 4.)GOVERNING CODE SHOULD INCLUDE 2007 |
| REVISIONS/SUPPLEMENTS, FS553.ALSO SEE MP4, REFERS TO |
| COUNTY AMENDMENTS TO THE STANDARD BUILDING CODE.OTHER |
| CODE REFERENCES ON THIS PAGE ARE INCORRECT OR OUTDATED. |
| CHECK ALL. |
| |
| 5.)PROVIDE A SURVEY FOR THIS PARCEL.THE SITE PLANS |
| PROVIDED ARE NOT CONSISTENT. |
| |
| 6.)PROVIDE A SOILS INVESTIGATION REPORT FBC1802.2. |
| TWO ORIGINALS REQUIRED. |
| |
| 7.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| FBC*106.3.3. |
| |
| 8.)PARKING STRIPING IS TO COMPLY WITH CITY OF WEST |
| PALM BEACH STANDARD, SEE ATTACHED DETAIL.REVISE C1. |
| |
| 9.)ACCESSIBLE PARKING SIGNAGE IS TO COMPLY WITH |
| FBC11-4.6.4; THE SIGN IS TO ALSO INCLUDE THE PENALTY. |
| REVISE C1 AND AB DESIGN SHEET 1 OF 3. |
| |
| 10.)BUILDING INFORMATION IS TO STATE WHETHER THE |
| BUILDING IS SPRINKLERED OR UN SPRINKLERED. |
| |
| 11.)BUILDING INFORMATION STATES THAT THE EXISTING |
| BUILDING IS F1, NEW USE IS SHOWN AS WAREHOUSE WHICH |
| WOULD BE STORAGE OCCUPANCY,FBC 311.NOTE CHANGE OF |
| OCCUPANCY ON THE PLAN; THIS JOB WILL BE REQUIRED TO |
| COMPLY WITH FBC EB CHAPTER 8. |
| |
| 12.)OCCUPANCY CALCULATIONS SHEET C1 STATE THAT THIS |
| IS M, OTHER PLACES DECLARE THIS AS B BUT ALSO STATE |
| THAT THIS IS STORAGE, GARAGE, AND WAREHOUSE.SEE FBC |
| 302.1, PORTIONS OF BUILDINGS TO BE CLASSIFIED WITH |
| RESPECT TO OCCUPANCY.DECLARE OCCUPANCY CLASSIFICATION |
| AND SUB CLASSIFICATION FOR EACH AREA AS WELL AS SQUARE |
| FOOT AREA FOR EACH OCCUPANCY. |
| |
| 13.)FOR THE STORAGE OCCUPANCIES (WAREHOUSE, STORAGE, |
| GARAGE), DECLARE S1 AND S2 WITH SQUARE FOOT AREAS FOR |
| EACH, SEE FBC311.2, FBC406. |
| |
| 14.)DECLARE OCCUPANT LOAD FOR EACH AREA, FBC1004. |
| |
| 15.)IS THIS BUILDING FOR ONE TENANT OR MULTIPLE |
| TENANTS?NOTE THIS INFORMATION ON THE PLAN AND SHOW |
| TENANT SEPARATION IF REQUIRED.NO SEPARATION SHOWN |
| BETWEEN THE OFFICE, BAY 1, AND BAY 2. |
| |
| 16.)PROPERTY APPRAISER WEBSITE AND AB DESIGN SHOWS |
| THE EXISTING BUILDING AS 1710 SF, ENGINEER SHOWS THIS |
| BUILDING AS 1438 ON C1.EITHER REVISE OR PROVIDE |
| INFORMATION TO SHOW WHY ENGINEER?S SQUARE FOOT TOTAL |
| CONFLICTS WITH PAPA AND LANDSCAPE ARCHITECT. |
| |
| 17.)THIS BUILDING APPEARS TO BE A MIXED OCCUPANCY |
| FBC302, PLEASE DECLARE AS SUCH AND DECLARE AS EITHER |
| SEPARATED OR NON SEPARATED USE. |
| |
| 18.)EXISTING BUILDING DECLARES THIS AS BUILDING TYPE |
| IIB, BUT A1 SHOWS FIRE DAMAGED WOOD GIRDER, OTHER WOOD |
| STRUCTURAL ELEMENTS, AND S4 SHOWS PT WOOD BUCKS.TYPE |
| II IS NONCOMBUSTIBLE CONSTRUCTION; SEE ALSO FBC603. |
| |
| 19.)SEE FBC TABLES 601, 602, 704.8.COMPLIANCE IS TO |
| BE SHOWN ON THE PLAN. |
| |
| 20.)EE-S3, F-S3, ANY OTHER APPLICABLE DETAILS, |
| SPECIFY THE WELDS. |
| |
| 21.)AB DESIGN LLC HAS AN APPLICATION PENDING FOR THE |
| BUSINESS LICENSE.UNTIL THIS IS ISSUED, THIS COMPANY |
| NAME CANNOT BE USED ON PLANS. |
| |
| 22.)SHOW ALL REQUIRED DETECTABLE WARNINGS, |
| FBC11-4.29. |
| |
| 23.)SHOW THE SIDEWALK WIDTH ON THE PLAN, SIDEWALK |
| BETWEEN ACCESSIBLE PARKING AND THE BUILDING.C1 SHOWS |
| A 44INCH SIDEWALK, WITH A NOTE ?SIDEWALK AS SHOWN ON |
| PLAN? BUT THE ENGINEER?S PLAN DOESN?T SHOW ANY |
| SIDEWALKS.THE LANDSCAPE ARCHITECT?S PLAN DOES NOT |
| DIMENSION THE SIDEWALK ALTHOUGH IT IS THE ACCESSIBLE |
| ROUTE, AND THERE IS A CONFLICT BETWEEN THE PARKING |
| DETAIL AND THE PARKING SHOWN ON THE SITE PLAN, BOTH ON |
| AB DESIGN PAGE 1.THE PARKING DETAIL SHOWS A VEHICLE |
| OVERHANG, PLAN SHOWS A WHEEL STOP.SEE FBC11-4.6.3, |
| VEHICLE OVERHANGS CANNOT REDUCE THE CLEAR WIDTH. DESIGN |
| INTENT IS NOT CLEAR. |
| |
| 24.)N/A |
| |
| 25.)IS THE LANDSCAPE ARCHITECT TAKING RESPONSIBILITY |
| FOR COMPLIANCE WITH FBC CHAPTER 11, FBC TABLE 601, 602, |
| 704.8 AS THE ENGINEER HAS NOT PROVIDED A SITE PLAN |
| SHOWING THE INFORMATION REQUIRED TO DETERMINE CODE |
| COMPLIANCE?ON THE SITE PLAN, DECLARE GOVERNING CODE |
| FS553. |
| |
| 26.)SEE FIGURE 11-7(6), TURNS AROUND AN OBSTRUCTION, |
| AND DOOR 3 INTO THE GARAGE, FBC11-4.3.3. |
| |
| 27.)LABEL EACH ROOM AS TO USE, AREAS BEHIND THE |
| BIFOLD DOORS 9 AND 10. |
| |
| 28.)SHOW THE ELEVATION ON EACH SIDE OF THE EXTERIOR |
| DOORS, FBC11-4.13.8. |
| |
| 29.)IF 9 AND 10 ARE CLOSETS, THESE AREAS ARE TO BE |
| ACCESSIBLE, SEE FBC11-4.25. |
| |
| 30.)THE SHOWER IS TO COMPLY WITH FBC 11-4.23, |
| FBC11-4.1.2(6).PROVIDE A DETAIL AND SHOW TURNING |
| RADIUS. |
| |
| 31.)PROVIDE DETAILS FOR THE TOILETS, LAVATORIES, GRAB |
| BARS, MIRRORS, FBC 11. |
| |
| 32.)SHOW CLEAR FLOOR SPACE FOR ALL FIXTURES AND |
| CLOSETS. |
| |
| 33.)PROVIDE A DETAIL FOR THE BREAK ROOM SINK SHOWING |
| COMPLIANCE WITH ALL REQUIREMENTS OF FBC11-4.24. |
| |
| 34.)THE BATHROOM AT DOOR 4 IS TO BE ACCESSIBLE, |
| FBC11-4.1.2(6). |
| |
| 35.)SHOW MANEUVERING CLEARANCE, PULL SIDE, FBC FIGURE |
| 11-25 DOORS 3, 6, 7. |
| |
| 36.)INTERIOR FINISHES TO COMPLY WITH FBC TABLE 803.5. |
| IT APPEARS TO BE COMPLIANT BUT CANNOT BE CONFIRMED |
| UNTIL SPRINKLER AND OCCUPANCY INFORMATION HAS BEEN |
| CONFIRMED. |
| |
| 37.)BUILDING INFORMATION, C1, ITEM 8 NEW ADDITION |
| STATES NON RATED, TABLE 302.3.2.THIS CODE SECTION IS |
| FOR SEPARATED USE WHICH WOULD REQUIRE A FIRE RATED |
| SEPARATION.SEE FBC 302.3.1, CORRELATE INFORMATION AND |
| REVISE PLAN AS NECESSARY. |
| |
| 38.)SPECIFY COMPONENTS AND CLADDING PRESSURES FOR THE |
| ROOF. |
| |
| 39.)PROVIDE A DETAIL FOR THE AC UNIT CURB, FBC1609. |
| |
| 40.)A NON IMPACT GLASS DOOR PRODUCT APPROVAL WAS |
| SUBMITTED.SEE FBC10 FBC1003.6, MEANS OF EGRESS |
| CONTINUITY.THE PATH OF EGRESS TRAVEL ALONG A MEANS OF |
| EGRESS SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT |
| OTHER THAN A MEANS OF EGRESS COMPONENT AS SPECIFIED IN |
| CHAPTER 10.YOU CANNOT BLOCK EXIT DOORS WITH A |
| HURRICANE SHUTTERS. |
| |
| 41.)FOR THE ROOF, SELECT THE APPROVED ASSEMBLY AND |
| SPECIFY ENHANCED FASTENING FOR ZONES 2 AND 3.THIS CAN |
| BE DONE AT THE TIME OF ROOF PERMIT APPLICATION. |
| |
| 42.)SOME OF THE NOAS SUBMITTED ARE DIFFICULT TO READ. |
| PLEASE PROVIDE LEGIBLE COPIES.THEY MAY BE AVAILABLE |
| AT WWW.BUILDINGCODEONLINE.COM. |
| |
| 43.)THE EASTERN METAL PRODUCT APPROVAL IS ILLEGIBLE. |
| PROVIDE LEGIBLE COPIES. |
| |
| 44.)SEE ATTACHED INSTALLATION SCHEDULE AND COMPLETE |
| THIS FORM (REQUIRED FOR HURRICANE SHUTTERS). |
| |
| 45.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL |
| PROPERTIES REQUIRES APPROVAL FROM THE BUILDING |
| OFFICIAL.IF YOU ARE PROPOSING TO USE REMOVABLE |
| SHUTTERS, SUBMIT A HURRICANE INSTALLATION PLAN, SEE |
| ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT APPROVALS |
| AND COMPLETE AN INSTALLATION SCHEDULE. |
| |
| THE INSTALLATION PLAN MAY BE SENT VIA EMAIL PRIOR TO |
| RESUBMITTAL OF THE PLANS.CONTRACTOR IS ENCOURAGED TO |
| GET THIS ISSUE RESOLVED PRIOR TO RESUBMITTAL TO AVOID |
| DELAYS IN PERMITTING. |
| |
| 46.)THE PRODUCT APPROVALS FOR THE STORM PANELS ARE |
| EXPIRED, FBC2001 RATHER THAN FBC2004.CURRENT |
| APPROVALS REQUIRED FAC9B72. |
| |
| 47.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG |