Plan Review Notes
Plan Review Notes For Permit 08020666
Permit Number 08020666
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-04-11 15:54:38*****UNSAT*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW COMMENTS STILL NEED TO BE ADDRESSED:
  
  
 5.THE OCCUPANT LOAD (0) LISTED IN THE GENERAL NOTES
 ON THE STRUCTURAL SHEET IS INCORRECT.BASED UPON
 OCCUPANCY TYPE,LIST THE OCCUPANT LOAD AS PER NFPA
 101, LIFE SAFETY CODE
  
 7.HOW WILL FIRE SPRINKLER PROTECTION ABOVE AND
 UNDERNEATH THE MEZZANINE BE ACHIEVED?
  
 *NEW COMMENT:
  
 A.ANY LOOSE PLAN SHEET(S) SHALL BE ATTACHED TO THE
 SUBMITTED PLAN SET(S).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW