Date Text
2008-04-11 11:00:39 
  
 BUILDING PLAN REVIEW
 PERMIT: 08020666
 ADD: 1335 OLD OKEECHOBEE RD
 CONT: MAURO BROTHERS LLC
 TEL: (561)738-4713
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4-11-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 **THIS INFORMATION SHALL BE SHOWN ON PLANS.**
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)OK
 5)OK
  
 6)CLEARLY INDICATE THE TOTAL SQUARE FOOT OF THE AREA
 WHERE THE MEZZANINE WILL BE CONSTRUCTED, AND SHOW THE
 ENTIRE FLOOR PLAN ON THE STRUCTURAL DRAWINGS. THE
 BUILDING TYPE SHALL BE INDICATED ON THE DRAWINGS PER
 TABLE 601.
  
 **THE 8X11 SHEET ATTACHED TO THE DRAWINGS SHOWS THE
 AREA OF THE MEZZANINE HOWEVER, THE TOTAL SQUARE FOOT OF
 THE SUITE IS NOT INDICATED AS REQUESTED AND THE ENTIRE
 FLOOR PLAN IS NOT SHOWN. ARE THERE ANY OFFICES BELOW
 THE MEZZANINE? IF SO PLEASE SHOW THE FLOOR PLAN FOR THE
 OFFICE AREA AND ELEVATION DRAWINGS OF THE OFFICES. WHAT
 IS THE FIRE RATING OF THE PARTITION WALLS SEPARATING
 EACH SUITE? **
  
 **THE BUILDING TYPE NOTED ON THE PLANS IS TYPE 1. TYPE
 1 BUILDINGS ARE CONSTRUCTED WITH NONCOMBUSTIBLE
 MATERIALS. FBC 602.2 AND TABLE 601. SEE SECTION 603
 WHERE FIRE-RETARDANT- TREATED WOOD IS PERMITTED IN SOME
 SITUATIONS. STATE THE HEIGHT OF THE BUILDING ON THE
 PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676
 [email protected]
  
  
  
  
  