Plan Review Notes
Plan Review Notes For Permit 08020666
Permit Number 08020666
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-10 15:08:32*****DENIED*****
  
  
 1.THE CORRECT ADDRESS, INCLUDING THE SUITE NUMBER,
 SHALL BE LISTED IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.PLEASE BE ADVISED OF THE FOLLOWING:(A)
 SUITE 200 IS SHOWN ON PLAN SHEET FP-1 INSTEAD OF SUITE
 600(B) THE JOB SITE ADDRESS IS IN WEST PALM BEACH AND
 NOT PALM BEACH AS LISTED IN THE TITLE BLOCK ON SHEETS
 E-1 AND E-2.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED
 DURING THE SCOPE OF WORK.IF SO, MEANS OF EGRESS AND
 AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN
 PLACE AND CONTINUOUSLY MAINTAINED.
  
 5.PLEASE LIST THE FOLLOWING FOR THE BUILDING:
 OCCUPANCY TYPE,OCCUPANT LOAD,FIRE ALARM AND/OR FIRE
 SPRINKLER DEVICES, AND ANY OTHER PERTINENT
 INFORMATION.
  
 6.PLEASE PROVIDE A CLEAR REPRENSENTATION OF THE
 MEZZANINE IN RELATION TO THE FLOOR PLAN INCLUDING EXIT
 LIGHTS/DOORS, EMERGENCY LIGHTS, ETC.
  
 7.HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE
 ALARM DEVICES, IF SO EQUIPPED.IN ADDITION. HOW WILL
 FIRE SPRINKLER PROTECTION UNDERNEATH THE MEZZANINE BE
 ACHIEVED?
  
 8.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved