Plan Review Notes
Plan Review Notes For Permit 08020666
Permit Number 08020666
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-04 09:24:03 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEET E-2 HAS THE "POWER DENSITY" AT 1.70 W/FT
 SQUARE. PER TABLE 13-415.2.C.1, THE MAXIMUM ALLOWABLE
 DENSITY WOULD BE 0.8, IN WHICH CASE THESE FIXTURES DO
 NOT COMPLY.
  
 2} INDICATE THE POWER SOURCE FOR THE EMERGENCY LIGHT ,
 UNDER POWER LOSS.
  
 3} THE DESCRIPTION OF WORK ON THEAPPLICATION
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718