Plan Review Notes
Plan Review Notes For Permit 08020666
Permit Number 08020666
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-06 12:26:25 
 BUILDING PLAN REVIEW
 PERMIT: 08020666
 ADD: 1335 OLD OKEECHOBEE RD
 CONT: MAURO BROTHERS LLC
 TEL: (561)738-4713
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3-6-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4)THE ENGINEER NEEDS TO INDICATE WHAT METHOD HE IS
 USING TO DESIGN THE MEZZANINE. THE DESIGN, FABRICATION
 AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS AND
 STRUCTURES SHALL BE IN ACCORDANCE WITH EITHER THE
 AISC-LRFD, AISC 335 OR AISC-HSS. FBC 2205.1. THE OPEN
 WEB JOIST SHALL BE IN ACCORDANCE WITH ONE OF THE
 FOLLOWING STEEL JOIST INSTITUTE SPECIFICATIONS: FBC
 2206.1
 1.STANDARD SPECIFICATIONS FOR OPEN WEB STEEL
 JOISTS, K SERIES.
 2.STANDARD SPECIFICATIONS FOR LONG SPAN STEEL
 JOISTS, LH SERIES AND DEEP LONG SPAN STEEL
 JOISTS, DLH SERIES.
 3.STANDARD SPECIFICATIONS FOR JOIST GIRDERS.
  
 5)F.A.C. 61G15-23.002 THE ENGINEER NEEDS TO SIGN,
 SEAL AND DATE PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL ENGINEER.
  
 6)CLEARLY INDICATE THE TOTAL SQUARE FOOT OF THE AREA
 WHERE THE MEZZANINE WILL BE CONSTRUCTED, AND SHOW THE
 ENTIRE FLOOR PLAN ON THE STRUCTURAL DRAWINGS. THE
 BUILDING TYPE SHALL BE INDICATED ON THE DRAWINGS PER
 TABLE 601.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561)805-6676
 [email protected]