2008-03-06 12:26:25 | |
| BUILDING PLAN REVIEW |
| PERMIT: 08020666 |
| ADD: 1335 OLD OKEECHOBEE RD |
| CONT: MAURO BROTHERS LLC |
| TEL: (561)738-4713 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 3-6-08 |
| REVIEW: 1ST |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4)THE ENGINEER NEEDS TO INDICATE WHAT METHOD HE IS |
| USING TO DESIGN THE MEZZANINE. THE DESIGN, FABRICATION |
| AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS AND |
| STRUCTURES SHALL BE IN ACCORDANCE WITH EITHER THE |
| AISC-LRFD, AISC 335 OR AISC-HSS. FBC 2205.1. THE OPEN |
| WEB JOIST SHALL BE IN ACCORDANCE WITH ONE OF THE |
| FOLLOWING STEEL JOIST INSTITUTE SPECIFICATIONS: FBC |
| 2206.1 |
| 1.STANDARD SPECIFICATIONS FOR OPEN WEB STEEL |
| JOISTS, K SERIES. |
| 2.STANDARD SPECIFICATIONS FOR LONG SPAN STEEL |
| JOISTS, LH SERIES AND DEEP LONG SPAN STEEL |
| JOISTS, DLH SERIES. |
| 3.STANDARD SPECIFICATIONS FOR JOIST GIRDERS. |
| |
| 5)F.A.C. 61G15-23.002 THE ENGINEER NEEDS TO SIGN, |
| SEAL AND DATE PLANS, SPECIFICATIONS, REPORTS OR OTHER |
| DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE |
| PROFESSIONAL ENGINEER. |
| |
| 6)CLEARLY INDICATE THE TOTAL SQUARE FOOT OF THE AREA |
| WHERE THE MEZZANINE WILL BE CONSTRUCTED, AND SHOW THE |
| ENTIRE FLOOR PLAN ON THE STRUCTURAL DRAWINGS. THE |
| BUILDING TYPE SHALL BE INDICATED ON THE DRAWINGS PER |
| TABLE 601. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| (561)805-6726 |
| FAX (561)805-6676 |
| [email protected] |