 1} THE VALUE ON THE APPLICATION MUSTINCLUDE THE TOTAL
 COST OF LABOR ANDMATERIAL FOR THE GENERATOR,
 EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.)AND PAD PER
 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHENRESUBMITTING, AND
 GET A RECEIPT FROM THEPERMIT CLERK.2}
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005 NEC.
  
 3} INDICATE THE SETBACK OF THE GENERATOR FROM THE
 GARAGE.
  
 4} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, METER ENCLOSURE, DISCONNECTS, ATS AND
 PANELS, SO THAT COMPLIANCE WITH ARTICLES 225 AND 230
 CAN BE REVIEWED.
  
 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  