Plan Review Notes For Permit 08020649 |
Permit Number |
08020649 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-03 09:36:16 | | | | | | | 1} THE VALUE ON THE APPLICATION MUSTINCLUDE THE TOTAL | | COST OF LABOR ANDMATERIAL FOR THE GENERATOR, | | EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.)AND PAD PER | | 108.3 FBC AS AMENDED. | | INCREASE THE VALUE AT THE COUNTER WHENRESUBMITTING, AND | | GET A RECEIPT FROM THEPERMIT CLERK.2} | | | | 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO | | BE SERVED. 215.5. 702.5, 2005 NEC. | | | | 3} INDICATE THE SETBACK OF THE GENERATOR FROM THE | | GARAGE. | | | | 4} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | A SITE PLAN, METER ENCLOSURE, DISCONNECTS, ATS AND | | PANELS, SO THAT COMPLIANCE WITH ARTICLES 225 AND 230 | | CAN BE REVIEWED. | | | | 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | REVIEW PER 106.1 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|