Plan Review Notes
Plan Review Notes For Permit 08020636
Permit Number 08020636
Review Stop E
Sequence Number 3
Notes
Date Text
2008-04-01 09:01:42** DENIED**
  
  
 1) NOTE: PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF COMPLETING.
 PLEASE SEE THAT ALL CIRCUITING NEEDS TO BE COMPLETE AND
 COORDINATE WITH THE PANEL SCHEDULES SUBMITTED OR TO BE
 SUBMITTED.
 FOR EXAMPLE: PLEASE SEE PLANS NOTE CIRCUIT 34 ON PANEL
 PH, YET NO PANEL PH WAS SUBMITTED.
 PLEASE SEE SHEET E2.1.2, THIS SHEET ALSO NOTES THE SAME
 *D* FIXTURES TO BE CONTINUED ON E2.1.1, HOWEVER WHEN
 YOU LOOK AT THE OTHER SHEET THE *D* FIXTURES ARE ON
 PANEL PH-2. PLEASE SEE THE LOAD ON THIS CIRCUIT IS
 SHOWN HIGHER THAN THE LOAD FOR THE THREE *D* FIXTURES
 SHOWN.
 PLEASE SEE THE FIXTURES WHICH ARE NOTED TO GO TO
 EXISTING EMERGENCY CIRCUIT DOES NOT INCLUDE LOAD,
 CIRCUIT, PANEL, LOCATION ETC?
  
 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND. FOR EXAMPLE:
 FIXTURE *B* WHICH DOES NOT SHOW ANY WATTAGE FOR BULB TO
 BE USED. LOAD CAN NOT BE DETERMINED FOR THIS CIRCUIT.
 ALMOST ALL LIGHTING IN DRIVE-THRU AREA IS SHOWN ON ONE
 CIRCUIT AND WITH OUT THIS INFORMATION THE CIRCUIT
 SIZING CAN NOT BE DETERMINED.
 THIS FIXTURE WAS LOOKED UP ON THE COMPANY?S WEB-SITE
 AND THIS FIXTURE HAS A WIDE RANGE OF WATTAGE. IF USING
 SOME OF THE HIGHER WATTAGE OF BULBS, THIS WOULD OVER
 LOAD THE CIRCUIT.
 PLEASE COMPLETE.
 NEC 220, 240.4, 310.16, ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE COMPLETE THE LOCATIONS OF NEW
 EQUIPMENT. PLEASE SEE THE ELECTRICAL ROOM AS SHOWN
 SHOWS TWO -2 TRANSFORMERS AND BOTH ARE SHOWN AS
 EXISTING. PLEASE ALSO SEE OTHER EQUIPMENT ON PLANS ALSO
 SHOWS OTHER EQUIPMENT AS EXISTING ALSO.
 PLEASE CLEARLY LABEL ALL EQUIPMENT AND SHOW LOCATIONS.
 110.26, 240.24, ETC
 FBC 106.1.2
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved