Plan Review Notes
Plan Review Notes For Permit 08020636
Permit Number 08020636
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-04 20:06:18** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE LOCATION IN WHICH THE SCOPE OF
 WORK HAS BEEN APPLIED FOR IS NOT CORRECT. THE LOCATION
 FOR SCOPE OF WORK IS 530 HIBISCUS. PERMIT APPLICATION
 SUBMITTED SHOWS 525 OKEECHOBEE BLVD ANDBASED ON THE
 PCN PLACED ON PERMIT APPLICATION AND AS APPLIED IN OUR
 SYSTEM THE APPLIED ADDRESS WAS 550 S. ROSEMARY
 PLEASE ADJUST PERMIT APPLICATION AND WHEN RESUBMITTING
 PLANS PLEASE BE SURE TO LET THE PERMIT COUNTER
 TECHNICIAN KNOW SO THAT ALL RELEVANT INFORMATION IN THE
 SYSTEM MAY BE CHANGED ACCORDINGLY. THIS WILL BE NOTED
 IN OTHER TRADE REVIEWS.
 PLEASE BE SURE ALL TITLE BLOCKS ON PLANS ARE ALSO
 ADJUSTED.
 FBC 106.5, FAC 61G1-16.004 ETC
  
 2) NOTE: PLANS ARE NOT COMPLETE AT THIS TIME FOR REVIEW
 OF APPLIED SCOPE OF WORK. PLEASE SEE THE FOLLOWING
 ITEMS.
 A) NO PANEL SCHEDULES WERE SUBMITTED. SIZE OF PANELS,
 LOADS ON PANELS EXISTING AND NEW ETC
 B) NO OVER CURRENT PROTECTION OF CIRCUITS WAS SHOWN
 C) STAIR TOWERS SHOW NEW FIXTURES WITH NO CIRCUITING
 FOR EMERGENCY AND EXIT LIGHTS
 D) PLEASE COMPLETE ALL CIRCUITING.
 408.4, 310.16, 220, 240.4, ETC
  
 3) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE
 CALCULATIONS FOR EXISTING AREA LIGHTING IN ORDER FOR
 ALLOWANCE OF NEW LIGHTING PER 13-415.2.
 PLEASE SUBMIT LIGHTING FIXTURE LEGEND AND COORDINATE
 WITH PLANS.
  
 4) NOTE: PLANS DO NOT SHOW ANY LIGHTING CONTROLS
 REQUIRED PER 13-415.1.ABC.1.4
  
 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR LIGHTING
 LEVELS AS REQUIRED UNDER FLORIDA STATUES FOR ATM
 LOCATIONS AND OTHER LIGHTING REQUIRED.
 FS 655.962.
  
 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIRS FOR
 MINIMUM COMPLIANCE WITH NFPA-101 2003 7.8.1.3, 7.9.2.2
  
 *** PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS
 NOT ON PLANS FOR REVIEW AND THERE MAY VERY WELL BE NEW
 COMMENTS ONCE PLANS ARE SUBMITTED COMPLETED FOR
 REVIEW.
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved