Date |
Text |
2008-03-04 20:06:18 | ** DENIEDREVIEW ** |
| |
| 1) NOTE: PLEASE SEE THE LOCATION IN WHICH THE SCOPE OF |
| WORK HAS BEEN APPLIED FOR IS NOT CORRECT. THE LOCATION |
| FOR SCOPE OF WORK IS 530 HIBISCUS. PERMIT APPLICATION |
| SUBMITTED SHOWS 525 OKEECHOBEE BLVD ANDBASED ON THE |
| PCN PLACED ON PERMIT APPLICATION AND AS APPLIED IN OUR |
| SYSTEM THE APPLIED ADDRESS WAS 550 S. ROSEMARY |
| PLEASE ADJUST PERMIT APPLICATION AND WHEN RESUBMITTING |
| PLANS PLEASE BE SURE TO LET THE PERMIT COUNTER |
| TECHNICIAN KNOW SO THAT ALL RELEVANT INFORMATION IN THE |
| SYSTEM MAY BE CHANGED ACCORDINGLY. THIS WILL BE NOTED |
| IN OTHER TRADE REVIEWS. |
| PLEASE BE SURE ALL TITLE BLOCKS ON PLANS ARE ALSO |
| ADJUSTED. |
| FBC 106.5, FAC 61G1-16.004 ETC |
| |
| 2) NOTE: PLANS ARE NOT COMPLETE AT THIS TIME FOR REVIEW |
| OF APPLIED SCOPE OF WORK. PLEASE SEE THE FOLLOWING |
| ITEMS. |
| A) NO PANEL SCHEDULES WERE SUBMITTED. SIZE OF PANELS, |
| LOADS ON PANELS EXISTING AND NEW ETC |
| B) NO OVER CURRENT PROTECTION OF CIRCUITS WAS SHOWN |
| C) STAIR TOWERS SHOW NEW FIXTURES WITH NO CIRCUITING |
| FOR EMERGENCY AND EXIT LIGHTS |
| D) PLEASE COMPLETE ALL CIRCUITING. |
| 408.4, 310.16, 220, 240.4, ETC |
| |
| 3) NOTE: PLEASE SEE NO LIGHTING PERFORMANCE |
| CALCULATIONS FOR EXISTING AREA LIGHTING IN ORDER FOR |
| ALLOWANCE OF NEW LIGHTING PER 13-415.2. |
| PLEASE SUBMIT LIGHTING FIXTURE LEGEND AND COORDINATE |
| WITH PLANS. |
| |
| 4) NOTE: PLANS DO NOT SHOW ANY LIGHTING CONTROLS |
| REQUIRED PER 13-415.1.ABC.1.4 |
| |
| 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR LIGHTING |
| LEVELS AS REQUIRED UNDER FLORIDA STATUES FOR ATM |
| LOCATIONS AND OTHER LIGHTING REQUIRED. |
| FS 655.962. |
| |
| 6) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIRS FOR |
| MINIMUM COMPLIANCE WITH NFPA-101 2003 7.8.1.3, 7.9.2.2 |
| |
| *** PLEASE KNOW AT THIS TIME THERE ARE SEVERAL ITEMS |
| NOT ON PLANS FOR REVIEW AND THERE MAY VERY WELL BE NEW |
| COMMENTS ONCE PLANS ARE SUBMITTED COMPLETED FOR |
| REVIEW. |
| |
| |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |