Plan Review Notes
Plan Review Notes For Permit 08020633
Permit Number 08020633
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-29 13:53:23 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 1} THE RISER DIAGRAM ON SHEET A-2 INDICATES "EXISTING",
 BUT NOTES PERTAINING TO THE RISER INDICATE LOCATION OF
 THE METER TO BE UNKNOWN. CLARIFY TO INDICATE IF
 EXISTING OR TO BE INSTALLED, ALSO LOCATE THE SERVICE
 EQUIPMENT ON THE PLAN.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6. IF IT IS
 DETERMINED TO BE AN EXISTING SERVICE THIS ISSUE MUST BE
 CORRECTED AS IT IS A LIFE SAFETY ISSUE.
  
 3}RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1)
 AND 210.52(A)(2). 2005 NEC. SEE REVIEWED PLAN FOR
 DEFICIENCIES IN THE NEW BEDROOM AND KITCHEN.
  
 4} A RECEPTACLE IS REQUIRED IN THE HALL/ENTRY PER
 210.52(H).
  
 5}210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.
  
 FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN THE
 FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE INDICATE
 THE CODE CYCLES UNDER WHICH THIS PLAN WAS DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718