Plan Review Notes For Permit 08020629 |
Permit Number |
08020629 |
|
Review Stop |
B |
Sequence Number |
6 |
|
Notes |
Date |
Text |
2009-04-06 10:37:53 | REVISED ADDITION FROM TWO STORY TO ONE STORY (4 REVISED | | PLAN SHEETS) | | | | BUILDING PROVISO | | | | 1) SUBMIT TWO (2) COPIES OF PRODUCT APPROVALS FOR THE | | FLAT ROOF. SPECIFY THE APPROVED ASSEMBLY, FASTENING | | OPTION AND DESIGN PRESSURE FOR THE SYSTEM THAT WILL BE | | INSTALLED. SUBMIT RAS 117 CALCULATIONS FOR THE ENHANCED | | FASTENING AT THE CORNER AND PERIMETER AREAS. FAC RULE | | 9B-72 | | | | 2) SUBMIT (2) COPIES REVISED ENERGY CALCULATIONS FOR | | THE REVISION TO A ONE STORY ADDITION. | | | | 3) SUBMIT SIGNED AND SEALED REVISED TRUSS DRAWINGS FOR | | THE FLAT ROOF THAT HAVE BEEN REVIEWED AND APPROVED BY | | THE DESIGNER OF RECORD FOR THE ADDITION. |
|