Plan Review Notes
Plan Review Notes For Permit 08020629
Permit Number 08020629
Review Stop B
Sequence Number 2
Notes
Date Text
2008-08-18 10:05:272004FBC W/2007 REVISIONS
 LEVEL 2 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) THE NOTICE OF COMMENCEMENT IS REQUIRED TO BE
 RECORDED AT THE COUNTY COURTHOUSE. A COPY OF THE
 RECORDED NOC WILL BE REQUIRED. FS 713
  
 2) SUBMIT A KEY PLAN INDICATING THE LOCATIONS OF THE
 OPENINGS LISTED ON THE STORM PANEL SCHEDULE. THE STORM
 PANEL SCHEDULE IS INCORRECTAND INCOMPLETE. THE
 CONNECTION TYPES ARE C1,C2,C3,C4 AND C5. FOR MINIMUM
 GLASS SEPARATION SEE TABLE 2 ON SHEET 4 OF THE PRODUCT
 APPROVAL NOA. IF THE HEIGHT OF THE WINDOW IS 52"AND
 THE PANELS ARE INSTALLED VERTICAL THE SPAN IS 56" NOT
 37".SPECIFY THE TOP AND BOTTOM ANCHOR SPACING.
 SPECIFY THE SUBSTRATE TO WHICH THE ANCHORS WILL BE
 ATTACHED.
 FBC R301.2.1.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]