2008-02-29 12:41:38 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 |
| FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| THE FOLLOWING: |
| |
| ALL COMMENTS REFER TO SHEET 3-5 UNLESS OTHERWISE |
| NOTED. |
| |
| 1} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| |
| 2} THE 20 AMP OCP AND #14 CONDUCTORS FOR CIRCUIT #13 DO |
| NOT COMPLY WITH 310.16. |
| |
| 3} THE LOADS GIVEN IN THE PANEL SCHEDULE FOR THE TWO |
| AHU' ARE SHOW AT 15500VA, BUT CALCULATED AT 10000 IN |
| THE CALCULATED LOAD TABLE, CORRELATE SAME. 220. |
| |
| 4} THE TWO BEDROOM CIRCUITS ARE LABELED AS GFCI ON THE |
| SCHEDULE, AND ARC FAULT IN THE NOTES. SEE 210.12. |
| |
| 5} THE DISCONNECT LOCATION AT THE CONDENSER DOES NOT |
| COMPLY WITH THE CLEARANCE REQUIREMENTS OF 110.26. ALSO |
| THERE WAS NO PLANS SUBMITTED FOR THE MECHANICAL WORK |
| THAT'S INTENDED, MORE COMMENTS MAY COME AT THAT TIME. |
| |
| 6} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| SHALL BE INTERCONNECTED AND HARD WIRED. SHOW LOCATIONS |
| AND ADD A NOTE TO INDICATE COMPLIANCE WITH THIS |
| ARTICLE. |
| |
| 7} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE |
| INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS |
| DESIGNED. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |