2008-03-04 11:40:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. THE PERMIT APPLICATION IS CONFUSING. THE SUBMITTED |
| INFORMATION IS INDICATING A SOLAR WATER HEATER HOWEVER |
| PERMIT APPLICATION DOES NOT INDICATE THIS OR HOW MANY |
| PANELS ARE TO BE INSTALLED OR THE SIZE OF THE SOLAR |
| STORAGE TANK. PLEASE CLAIFY AND CORRECT PERMIT |
| APPLICATION. NOTE: DESCRIBE PROJECT IN DETAIL (FAILURE |
| TO DO SO MAY RESULT IN DELAYS). PER CITY OF WPB |
| AMENDMENTS TO CHAPTER 1, SECTION 105 PERMITS. |
| |
| 2. CLEARLY IDENTIFY ALL COMPONENTS, PIPE SIZES, AND |
| SHUT OFF VALVES (PER FBC PLUMBING SECTION 606.1 |
| FULL-OPEN VALVES SHALL BE INSTALLED ON THE WATER SUPPLY |
| PIPE TO EVERY WATER HEATER) ON THE GUARDIAN'S SELF |
| SUFFICIENCY SHEET. DIAGRAM APPEARS TO BE INDICATING A T |
| & P RELIEF VALVE AND VACUUM RELIEF VALVE HOWEVER THEY |
| ARE NOT CLEARLY IDENTIFIED. PER CITY OF WPB AMENDMENTS |
| TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 3. CLEARLY INDICATE THE POTABLE COLD WATER SIZE AND |
| MAKEUP LOCATION TO THE SOLAR WATER HEATER AND THE |
| POTABLE HOT WATER SIZE AND DISCHARGE LOCATION TO THE |
| HOUSE ON THE GAURDIAN'S SELF SUFFICIENCY SHEET. PER FBC |
| PLUMBING SECTION 601.1 SCOPE. |
| |
| 4. WHAT IS THE SIZE OF THE SOLAR STORAGE TANK ON THE |
| GAURDIAN'S SELF SUFFICIENCY SHEET? PER FBC PLUMBING |
| SECTION 501.1 SCOPE. |
| |
| 5. THE VALUE ON THE PERMIT APPLICATION APPEARS TO BE |
| LOW. |
| PER FBC-2004, CHAPTER 1, SECTION |
| 108.3, BUILDING PERMIT VALUATION: IF IN |
| THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF THE BUILDING, |
| ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| TO BE UNDERESTIMATED ON THE APPLICATION, |
| THE PERMIT SHALL BE DENIED. FOR |
| PERMITTING PURPOSES, VALUATION OF |
| BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| FINISH, NORMAL SITE WORK (EXCAVATION AND |
| BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| VALUE. VALUATION REFERENCES MAY INCLUDE |
| THE LATEST PUBLISHED DATA OF NATIONAL |
| CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| MEANS ECT.) WITH |
| REGIONAL ADJUSTMENTS FOR LOCATION AS |
| PUBLISHED BY INTERNATIONAL CODE |
| CONGRESS. |
| |
| 6. PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS FOR ALL POTABLE SOLAR WATER HEATER |
| EQUIPMENT. PER CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1, SECTION 106.1.2 ADDITIONAL DATA. |
| |
| 7.PER FS 713.13 (1) THRU (6): A NOTICE OF |
| COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| HWY., BEFORE A PERMIT CAN BE ISSUED. |
| |
| |
| ****IMPORTANT INFORMATION****** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| PHONE= (561) 805-6730 |
| FAX= (561) 805-6731 |
| E-MAIL= [email protected] |