2008-03-25 16:59:09*****DENIED*****
  
  
 1.THE ADDRESS SHOWN ON THE TITLE SHEET (C-1) OF 300
 SEMINOLE AVENUE REFERS TO WHAT/WHERE?
  
 2.THE ADDRESS OF THE SCOPE OF WORK SITE SHALL BE IN
 THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.ON SHEET C-2 & C-3, THE VERBAGE OF "450 S
 AUSTRALIAN AV" IS SHOWN IN THE MIDDLE OF THE PARKING
 LOT.WHAT IS ITS PURPOSE FOR BEING THERE?
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH ACCESS TO/EGRESS FROM THE PROPERTY OR VICINITY
 THEREOF (INCLUDING STREETS, ROADS, FIRE LANES, ETC.) .
  
 6.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 7.PROVIDE THE OCCUPANCY TYPE AND OCCUPANT LOAD.
  
 8.SPECIFY THE WALL AND CEILING FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 9.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER IN THE NEW STRUCTURE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  