2008-03-08 20:12:49 | ** DENIED ** |
| |
| ** 400 S. AUSTRALIAN AVE. |
| PERMIT #08020505 |
| |
| ** A PRELIMINARY REVIEW WAS DONE AND PROVIDED TO THE |
| ENGINEER SEVERAL MONTHS AGO HOWEVER MOST OF THE SAME |
| ITEMS GIVEN ON THAT REVIEW ARE STILL THE SAME ON |
| PLANS. |
| |
| 1) NOTE: PERMIT APPLICATION SUBMITTED IS TO INSTALL NEW |
| ELECTRICAL HOWEVER THIS SCOPE OF WORK SHOULD HAVE BEEN |
| INCLUDED WITH OTHER SCOPE OF WORK AS APPLIED UNDER |
| OTHER PERMIT NUMBERS. |
| AS SUBMITTED, EACH SET OF PLANS SUBMITTED UNDER EACH |
| PERMIT WILL BE REQUIRED TO CONTAIN ALL OTHER |
| INFORMATION FROM OTHER PERMITS. AS EACH IS A SEPARATE |
| RECORD AND EACH HAS A DIRECT AFFECT ON THE OTHER |
| COMPLETE SETS WILL BE REQUIRED FOR ALL PERMITS. PLEASE |
| KNOW AS OF THIS REVIEW A NOTICE HAS BEEN SENT TO |
| BUILDING OFFICIAL ON HOW THE PERMITS WERE APPLIED. |
| PLEASE SEE REVIEWS UNDER OTHER APPLIED PERMITS. THESE |
| MAY ALL BE COMING IN UNDER CONSOLIDATE PERMIT(S) BEFORE |
| ALL REVIEWS ARE COMPLETED AND WITH RELEVANT SUB PERMITS |
| NEEDED. |
| PLANS AND ALL PERMIT APPLICATIONS AND DOCUMENTS AS |
| SUBMITTED ARE VERY CONFUSING AS APPLIED EVEN THOUGH |
| THIS REVIEWER UNDERSTANDS THE INTENT OF THE PROPOSED |
| TOTAL SCOPE OF WORK. |
| |
| 2) NOTE: PLEASE SUBMIT COMPLETE PLANS UNDER DESIGNS |
| FOR: |
| NFPA-70 2005 |
| NFPA-20 2003 |
| NFPA-110 2002 |
| NFPA-101 2003 |
| |
| ** THERE ARE TOO MANY ITEMS TO LIST ALL CODE VIOLATIONS |
| ON THIS LIST. THE FOLLOWING ARE SOME ITEMS. |
| |
| 3) NOTE: PLEASE SEE NFPA-20, THE FIRE PUMP DISCONNECT |
| AND SERVICE EQUIPMENT SHALL NOT BE LOCATED IN THE MAIN |
| ELECTRICAL ROOMS. |
| PLEASE ALSO SUBMIT COMPLETE INFORMATION FOR FPC, FP, |
| FOR LOCKED ROTOR OVER CURRENT PROTECTION ETC. PLEASE |
| SEE NEC 695.3, 695.4 AND NFPA-20 CHAPTERS 9 AND 10. |
| ETC |
| THERE ARE SEVERAL ITEMS WHICH CAN NOT BE REVIEWED FOR |
| CODE COMPLIANCE. |
| |
| 4) NOTE: PLEASE SEE 230.71, 230.70 AS NO MORE THAN 8FT |
| OF UNPROTECTED CONDUCTORS SHALL BE PERMITTED INSIDE THE |
| BUILDING. |
| |
| 5) NOTE: PLANS SHOWS THE REMOVAL OF THE UN-PERMITTED |
| GENERATOR FOR CELL SITE HOWEVER PLANS DO NOT PROVIDE |
| ENOUGH INFORMATION ON THIS UNIT. WILL THIS BE REMOVED |
| AND RE-INSTALLED UNDER SEPARATE PERMIT, PLANS ETC? |
| |
| 6) NOTE: PLEASE KNOW AS THE SEPARATE PERMIT WAS SUBMIT |
| FOR GENERATOR NOT ENOUGH INFORMATION FOR NEW LOADS ON |
| PROPOSED |
| ** AS PERMIT APPLICATION WAS SUBMITTED WITH OTHER |
| PERMIT APPLICATIONS FOR THIS SAME LOCATION, PLEASE SEE |
| ANY NOTES UNDER OTHER PERMITS WHICH WILL AFFECT OTHER |
| REVIEWS. |
| 700, 701, 702 |
| |
| 7) NOTE: PLEASE SEE NO RUN TIMES FOR ON-SITE FUEL WAS |
| SUBMITTED. PLEASE SEE NFPA-20 9.6.2.2 |
| |
| 8) NOTE: PLEASE SEE NFPA-110 ALL, AS THE GENERATOR DOES |
| FEED LIFE SAFETY AND LEGALLY REQUIRED LOADS.PLEASE |
| SEE 7 FOR LOCATIONS, ELEVATIONS, ETC |
| |
| 9) NOTE: PLEASE SEE PERMIT # 08020653 AS THE GENERATOR |
| APPLIED WAS FOR A JOHN DEERE GENERATOR AND THESE PLANS |
| SUBMITTED UNDER 08020505 ARE FOR A CATERPILLAR. THE |
| SIZE IS NOT THE SAME, ONE IS 150KW AND THE OTHER |
| 160KW. |
| |
| 10) NOTE: PLEASE SEE MUCH OF THE SERVICE EQUIPMENT AS |
| SHOWN DOES NOT CONTAIN ANY VOLTAGES. |
| NEC ALL, NFPA AS NOTED. |
| FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| |
| 11) NOTE: PLEASE SEE NFPA-110 AS THE LIFE SAFETY |
| SERVICE EQUIPMENT IS NOT PERMITTED INSIDE ELECTRICAL |
| ROOM AS SHOWN.7.1.3, 7.2.2, 7.2.2.1 |
| |
| 12) NOTE: PLEASE SEE NO LOAD INFORMATION AND ACTUAL TAP |
| LOCATIONS FOR NEW DP WAS LOCATED ON PLANS. |
| THE LOAD SUMMARY FOR ( MAIN #1, HOUSE AMPACITY ) DOES |
| NOT PROVIDE ENOUGH INFORMATION. |
| NEC 220.87 ETC |
| |
| 13) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH |
| RESPECT TO PROPOSED SHED. |
| |
| 14) NOTE:PLEASE KNOW THEVALUE SHALL INCLUDE ALL |
| LABOR, MATERIALS, EQUIPMENT, DESIGN COST ETC EVEN IF |
| ANY OF THESE ARE OWNER SUPPLIED. THIS INCLUDES THE |
| GENERATOR, ATS ETC. |
| |
| |
| ** THERE ARE MANY ITEMS WHICH ARE NEEDED AND MAY VERY |
| WELL BE COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| BE MADE AT THIS TIME. |
| |
| ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |