Date |
Text |
2008-02-21 13:25:05 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE |
| MITIGATION. |
| THE APPLICATION STATES THAT THE PLYWOOD JOINTS WILL BE |
| TAPED.DOES THIS APPLY TO BOTH THE FLAT AND THE |
| PITCHED ROOF SECTIONS? |
| |
| _XX_2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| EACH ROOF TYPE |
| |
| ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| _XX_4.)FOR THE FLAT ROOF, SELECT THE APPROVED |
| ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| LIMITATIONS. THE ASSEMBLY SELECTED IS A TILE |
| UNDERLAYMENT. |
| |
| _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| SHEET).THE ENHANCED FASTENING SUBMITTED IS A |
| PHOTOCOPY OF ENGINEERING WHICH REFERS TO A DIFFERENT |
| ASSEMBLY FROM THE ONE SELECTED.DOCUMENTS PREPARED BY |
| AN ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| SIGNED, SEALED, DATED ORIGINALS FS471. |
| |
| _XX_ 6.)TWO COMPLETE COLLATED SETS OF PERMIT |
| DOCUMENTS REQUIRED. |