Plan Review Notes For Permit 08020471 |
Permit Number |
08020471 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-05-01 14:20:32 | DENIED; | | 1. DRINKING FOUNTAIN NOT TO FBC-2004 BUILDING CHAPTER | | 11 ACCESSIBILITY CODE. | | A. FREE STANDING DRINKING FOUNTAINS IS | | PERMITED, SECTION 11-4.15.5 WITH A PARALLEL APPROACH, | | 30" X 48". THE LOCATION OF THE DRINKING FOUNTAIN DOES | | NOT ALLOW A PARALLEL APPROACH, WALL LEFT SIDE OF D/F | | PROTRUDES INTO THE CLEARE FLOOR SPACE. | | B. SUBMIT MANUFACTURE SPEC. SHEETS THAT SHOW | | ADA COMPLIANCE. SECTION 11-4.15.2, SPOUT HEIGHT SHALL | | BE NO HIGHER THAN 36". PLUMBING FIXTURE SCHEDULE LISTS | | THE HEIGHT OF D/F AS 40" HIGH. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|