Plan Review Notes
Plan Review Notes For Permit 08020471
Permit Number 08020471
Review Stop E
Sequence Number 2
Notes
Date Text
2008-03-25 10:09:44 
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE FLA/COM VERSION 3.00 SUBMITTED HAS NOT YET BEEN
 ADOPTED BY THE FBC. PLEASE SEE 13.400.3 REFERENCES
 VERSION 2.5.
  
 2} THE CERTIFICATION OF COMPLIANCE MUST BE SIGNED BY
 THE OWNER OR OWNER AGENT. SEE 103.1 (13-103.1) AND PAGE
 #3 OF THE CERTIFICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718