2008-02-25 10:51:40 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| *** DENIED *** |
| 1) SEE ELECTRICAL REVIEW NOTE #1, PLEASE CORRECT. |
| |
| 2) THE JOB ADDRESS NEEDS TO BE IN THE TITLE BLOCK ON |
| EACH PAGE ON THE PLANS, SEE W.P.B. AMEND. 106.1.3 AND |
| F.A.C. 61G1-16.004(3). |
| |
| 3) PLEASE SUBMIT PRODUCT APPROVAL OR AN NOA FOR 12X12 |
| WALL LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| 9B-72.005, AND FAC 9B-72.010(31)(G). |
| |
| **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| |
| *** PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED |
| IN WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL (A SHOP REVIEW STAMP AND |
| SIGNATURE WILL MEET THIS REQUIREMENT). SEE W.P.B. |
| AMEND. 106.3. |
| |