Plan Review Notes For Permit 08020471 |
Permit Number |
08020471 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-03 12:15:29 | *****DENIED***** | | | | 1.THE PROJECT SITE ADDRESS, INCLUDING THE SUITE | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET. | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 3.SPECIFY THE INTERIOR WALL AND CEILING FINISH | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 4.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS | | I OR CLASS II. | | | | 5.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL | | DISTANCE. | | | | 6.IT IS INDICATED ON SHEET FA1.01 THAT THE BUILDING | | IS FIRE SPRINKLERED.PLEASE SHOW THE LAYOUT OF THE | | SPRINKLER HEADS IN THE TENANT SPACE. | | | | 7.PLEASE EXPLAIN THE DOOR BETWEEN THE TWO TENANT | | SPACES.IF THESE ARE DIFFERENT SPACES, HOW WILL TENANT | | SEPARATION BE ACCOMPLISHED. | | | | 8.THE SCOPE OF WORK LOCATION ON SHEET A1 AND A2 DOES | | NOT CORRELATE WITH WHERE IS SHOWN ON THE OTHER | | SUBMITTED PLAN SHEETS. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|