2008-02-22 16:42:42 | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} SHEETS A1 AND A2 SHOW THE LOCATION OF THE WORK TO BE | | IN SUITE 102, THE MEP'S INDICATE WORK IN SUITE 103. | | CORRELATE WORK AREA INTENDED, THE APPLICATION ALSO | | INDICATES 103. | | | | 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR | | SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE | | SHOWN ON THE PLAN. | | | | 3} PROVIDE LIGHTING POWER DENSITY COMPLIANCE ON THE | | PLAN, CORRELATING WITH FIXTURE TYPES. NOTE THAT THE | | FORM400A IS FOR "WHOLE BUILDING" AND CANNOT BE USED FOR | | AN INTERIOR BUILD OUT OR RENOVATION AS THIS IS | | OBVIOUSLY NOT THE "WHOLE BUILDING". | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|