2008-02-22 16:42:42 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} SHEETS A1 AND A2 SHOW THE LOCATION OF THE WORK TO BE
 IN SUITE 102, THE MEP'S INDICATE WORK IN SUITE 103.
 CORRELATE WORK AREA INTENDED, THE APPLICATION ALSO
 INDICATES 103.
  
 2} INDICATE COMPLIANCE WITH 13-415.1ABC.1.2, FBC FOR
 SPACE CONTROLS FOR LIGHTING." STANDARD SWITCHES ARE
 SHOWN ON THE PLAN.
  
 3} PROVIDE LIGHTING POWER DENSITY COMPLIANCE ON THE
 PLAN, CORRELATING WITH FIXTURE TYPES. NOTE THAT THE
 FORM400A IS FOR "WHOLE BUILDING" AND CANNOT BE USED FOR
 AN INTERIOR BUILD OUT OR RENOVATION AS THIS IS
 OBVIOUSLY NOT THE "WHOLE BUILDING".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718