2008-02-29 07:54:32 | PERMIT: 08020471 |
| ADD: 2475 MERCER AVE #103 B |
| CONT: CUSTOM QUALITY HOMES INC. |
| TEL: (561)747-2620 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST 2-29-08 |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| BUILDING PLAN REVIEW |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| BUILDING WITH THE 2007 SUPPLEMENTS. |
| |
| 4) 11-4.13.6. MINIMUM MANEUVERING CLEARANCES AT DOORS |
| THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| SHOWN IN FIG.25. THE FLOOR OR GROUND AREA WITHIN THE |
| REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL. |
| |
| |
| 5)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS |
| DETERMINED BY THE BUILDING OFFICIAL. IT SEEMS AS IF |
| THERE ARE DIFFERENT SUITES / UNITS AT THIS ADDRESS WITH |
| DIFFERENT NUMBERS WHICH WILL REQUIRE SEPARATE PERMITS: |
| THE PLANS SHOW A DOOR CONNECTING TWO UNITS. INDICATE |
| CLEARLY IF THESE TWO SUITES WILL BE OWNED AND OPERATED |
| BY ONE TENANT: IF NOT THE DOOR SHALL BE ELIMINATED, AND |
| BE REPLACE WITH THE REQUIRED SEPARATION PARTITION PER |
| FBC 708 AND TABLE 302.3.2. PLEASE BE SURE THE PLANS AND |
| APPLICATION HAS THE CORRECT SUITE NUMBERS, BECAUSE |
| THERE ARE TWO APPLICATIONS WITH THE SAME DRAWINGS WHICH |
| SHOW THE WORK IN THE SAME LOCATION AND THE UNIT AS |
| #102. FOR MORE INFORMATION ABOUT THE ADDRESSING PLEASE |
| CONTACT LILLI @ 822-1239. |
| |