Plan Review Notes
Plan Review Notes For Permit 08020471
Permit Number 08020471
Review Stop B
Sequence Number 1
Notes
Date Text
2008-02-29 07:54:32PERMIT: 08020471
 ADD: 2475 MERCER AVE #103 B
 CONT: CUSTOM QUALITY HOMES INC.
 TEL: (561)747-2620
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-29-08
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 BUILDING PLAN REVIEW
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 4) 11-4.13.6. MINIMUM MANEUVERING CLEARANCES AT DOORS
 THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG.25. THE FLOOR OR GROUND AREA WITHIN THE
 REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
  
 5)FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. IT SEEMS AS IF
 THERE ARE DIFFERENT SUITES / UNITS AT THIS ADDRESS WITH
 DIFFERENT NUMBERS WHICH WILL REQUIRE SEPARATE PERMITS:
 THE PLANS SHOW A DOOR CONNECTING TWO UNITS. INDICATE
 CLEARLY IF THESE TWO SUITES WILL BE OWNED AND OPERATED
 BY ONE TENANT: IF NOT THE DOOR SHALL BE ELIMINATED, AND
 BE REPLACE WITH THE REQUIRED SEPARATION PARTITION PER
 FBC 708 AND TABLE 302.3.2. PLEASE BE SURE THE PLANS AND
 APPLICATION HAS THE CORRECT SUITE NUMBERS, BECAUSE
 THERE ARE TWO APPLICATIONS WITH THE SAME DRAWINGS WHICH
 SHOW THE WORK IN THE SAME LOCATION AND THE UNIT AS
 #102. FOR MORE INFORMATION ABOUT THE ADDRESSING PLEASE
 CONTACT LILLI @ 822-1239.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]