Plan Review Notes For Permit 08020470 |
Permit Number |
08020470 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-08-13 14:34:10 | *** PROVISO *** | | 1) AIR HANDLER SHALL COMPLY WITH 2004 FBC/M 306.3. | | ATTICS CONTAINING APPLIANCES REQUIRING ACCESS SHALL BE | | PROVIDED WITH AN OPENING AND UNOBSTRUCTED PASSAGEWAY | | LARGE ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE. | | THE PASSAGEWAY SHALL NOT BE LESS THAN 30 INCHES (762 | | MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE THAN | | 6 FEET (1829 MM) IN LENGTH MEASURED ALONG THE | | CENTERLINE OF THE PASSAGEWAY FROM THE ATTIC ACCESS | | OPENING TO THE APPLIANCE?S SERVICE PANEL. THE | | PASSAGEWAY SHALL HAVE CONTINUOUS SOLID FLOORING NOT | | LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE | | SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30 | | INCHES (762 MM) WIDE SHALL BE PRESENT AT THE FRONT OR | | SERVICE SIDE OF THE APPLIANCE. THE CLEAR ACCESS OPENING | | DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES | | (508 MM BY 762 MM), WHERE SUCH DIMENSIONS ARE LARGE | | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE. | | | | EXCEPTION: THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE | | NOT REQUIRED WHERE THE APPLIANCE IS CAPABLE OF BEING | | SERVICED AND REMOVED THROUGH THE REQUIRED OPENING. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|