Plan Review Notes
Plan Review Notes For Permit 08020470
Permit Number 08020470
Review Stop M
Sequence Number 4
Notes
Date Text
2008-08-13 14:34:10*** PROVISO ***
 1) AIR HANDLER SHALL COMPLY WITH 2004 FBC/M 306.3.
 ATTICS CONTAINING APPLIANCES REQUIRING ACCESS SHALL BE
 PROVIDED WITH AN OPENING AND UNOBSTRUCTED PASSAGEWAY
 LARGE ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
 THE PASSAGEWAY SHALL NOT BE LESS THAN 30 INCHES (762
 MM) HIGH AND 22 INCHES (559 MM) WIDE AND NOT MORE THAN
 6 FEET (1829 MM) IN LENGTH MEASURED ALONG THE
 CENTERLINE OF THE PASSAGEWAY FROM THE ATTIC ACCESS
 OPENING TO THE APPLIANCE?S SERVICE PANEL. THE
 PASSAGEWAY SHALL HAVE CONTINUOUS SOLID FLOORING NOT
 LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE NOT LESS THAN 30 INCHES (762 MM) DEEP AND 30
 INCHES (762 MM) WIDE SHALL BE PRESENT AT THE FRONT OR
 SERVICE SIDE OF THE APPLIANCE. THE CLEAR ACCESS OPENING
 DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY 30 INCHES
 (508 MM BY 762 MM), WHERE SUCH DIMENSIONS ARE LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE.
  
 EXCEPTION: THE PASSAGEWAY AND LEVEL SERVICE SPACE ARE
 NOT REQUIRED WHERE THE APPLIANCE IS CAPABLE OF BEING
 SERVICED AND REMOVED THROUGH THE REQUIRED OPENING.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]