2008-03-27 13:27:07PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 1.THE DRINKING FOUNTAIN IS REQUIRED TO BE ACCESSIBLE.
 THE OASIS DRINKING FOUNTAIN MODEL #P3CP IS NOT A
 HANDICAP APPROVED FIXTURE. THE LOCATION OF THE DRINKING
 FOUNTAIN WILL ALLOW A FRONTAL. SHOW THE CLEAR FLOOR
 SPACE ON THE PLANS (SHEET P1.01) 30" X 48". PLEASE
 REVIEW FBC BUILDING CHAPTER 11, SECTIONS 11-4.15.1 THRU
 11-4.15.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  