Plan Review Notes
Plan Review Notes For Permit 08020439
Permit Number 08020439
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-04 12:25:45*****DENIED******
  
  
 1.ON SHEET 1 OF 1, AMEND FIRE ALARM SEQUENCE OF
 OPERATION TO REFLECT THAT DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM.
  
 2.ON SHEET 1 OF 1, INCLUDE THE INSTALLATION OF THE
 FIRE ALARM ANNUNCIATOR (FAA) IN THE TOTAL SCOPE OF
 WORK.
  
 3.ON SHEET 1 OF 1, THERE ARE 22 HORN STROBES
 INSTALLED ACCORDING TO THE SCOPE OF WORK AND THE
 LEGEND/EQUIPMENT LIST. IT APPEARS THAT ONLY 21 SUCH
 DEVICES ARE SHOWN ON THE FIRE ALARM LAYOUT (SHEET 1)
 AND THE FIRE ALARM RISER (SHEET 2).
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  