 PROVISO
 SHEET E3.01
 IF THE EQUIPMENT GROUNDING CONDUCTOR AND THE GROUNDED
 CONDUCTOR ARE BONDED TO THE GROUNDING ELECTRODE
 CONDUCTOR IN THE GUTTER, THE EQUIPMENT GROUND AND THE
 GROUNDED CONDUCTOR (NEUTRAL), MUST BE ISOLATED FROM
 THAT POINT THROUGHOUT THE REST OF THE SYSTEM. IF ONLY
 THE GROUNDED CONDUCTOR IS BONDED TO THE GROUNDING
 ELECTRODE AND THE GUTTER, THE GROUNDED CONDUCTOR MUST
 BE RAN TO THE DISCONNECT, AND THE #6 EQUIPMENT GROUND,
 SHOWN RAN FROM THE GUTTER TO THE DISCONNECT, SHALL NOT
 BE INSTALLED AS THEY PROVIDE A PARALLEL GROUNDING PATH
 THAT COULD ENERGIZE ALL METAL PARTS IN THE SYSTEM.
 250.6, 250.24(B) AND (C).
  