Plan Review Notes
Plan Review Notes For Permit 08020396
Permit Number 08020396
Review Stop B
Sequence Number 1
Notes
Date Text
2008-02-23 12:43:40BUILDING PLAN REVIEW
 PERMIT: 08020396
 ADD: 2945 AUSTRALIAN AVE. SUITE C
 CONT: PETRA BUILDERS INC.
 TEL: (561)361-7570
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-23-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL
 FOR THE NEW DOOR.
  
 3)THE FINISH FLOORS IN THE BATHROOM SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD
 ONTO THE WALLS AT LEAST 6 INCHES FBC 1210.1. ALL WALLS
 WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF 4
 FEET FBC 1210.2. NOTE: PAINT ON DRYWALL IN NOT
 CONSIDERED A HARD SURFACE. STATE ON THE FINISH SCHEDULE
 WHAT TYPE OF MATERIALS WILL BE USED TO MEET THESE
 REQUIREMENTS.
  
 4)SUBMIT THE DETAIL DRAWINGS FOR THE C.M.U. AND METAL
 STUD WALLS. THE C.M.U. WALL DETAIL SHALL SHOW HOW THE
 NEW INFILL WALLS WILL TIE INTO THE EXISTING WALLS
 SHOWING ALL WALL TIES, STEEL ETC FBC 2109.6.3. A DETAIL
 DRAWING IS ALSO REQUIRED FOR THE NEW 36 INCHES C.M.U.
 WALL.
  
 5) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL
 NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP
 SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL
 CLEARANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]