2008-02-23 12:43:40 | BUILDING PLAN REVIEW |
| PERMIT: 08020396 |
| ADD: 2945 AUSTRALIAN AVE. SUITE C |
| CONT: PETRA BUILDERS INC. |
| TEL: (561)361-7570 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST 2-23-08 |
| ACTION: DENIED |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 2)106.3.3* PRODUCT APPROVALS- 2004. THOSE PRODUCTS |
| THAT ARE REGULATED BY DCA |
| RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL |
| FOR THE NEW DOOR. |
| |
| 3)THE FINISH FLOORS IN THE BATHROOM SHALL HAVE A |
| SMOOTH, HARD, NONABSORBENT SURFACE THAT EXTENDS UPWARD |
| ONTO THE WALLS AT LEAST 6 INCHES FBC 1210.1. ALL WALLS |
| WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A |
| SMOOTH, HARD, NONABSORBENT SURFACE TO A HEIGHT OF 4 |
| FEET FBC 1210.2. NOTE: PAINT ON DRYWALL IN NOT |
| CONSIDERED A HARD SURFACE. STATE ON THE FINISH SCHEDULE |
| WHAT TYPE OF MATERIALS WILL BE USED TO MEET THESE |
| REQUIREMENTS. |
| |
| 4)SUBMIT THE DETAIL DRAWINGS FOR THE C.M.U. AND METAL |
| STUD WALLS. THE C.M.U. WALL DETAIL SHALL SHOW HOW THE |
| NEW INFILL WALLS WILL TIE INTO THE EXISTING WALLS |
| SHOWING ALL WALL TIES, STEEL ETC FBC 2109.6.3. A DETAIL |
| DRAWING IS ALSO REQUIRED FOR THE NEW 36 INCHES C.M.U. |
| WALL. |
| |
| 5) 11-4.8.4.(2) LANDINGS. ALL LANDINGS ON RAMPS SHALL |
| NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH RAMP |
| SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL |
| CLEARANCE. |
| |