2008-04-24 14:07:19PLUMBING PLAN REVIEW:
 DENIED **2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE
 OF CONTINUITY.
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (TWO COPIES OF MANUFACTURE
 SHEETS REQUIRED INDICATING THE MAKE, MODEL NUMBER, AND
 A LISTING FROM A NATIONALLY RECOGNIZED TESTING AGENCY,
 PLEASE SUBMIT)
 **THE RESUBMITTAL DID NOT HAVE 2 COPIES OF THE POOL
 HEATER MANUFACTURER'S SHEETS INDICATING THE MAKE, MODEL
 NUMBER AND A LISTING FROM A NATIONALLY RECGNIZED
 TESTING LABORATORY.
  
 END OF COMMENTS:
  