2008-08-25 14:42:32 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ALL COMMENTS RELATE TO SHEET E1, UNLESS OTHERWISE
 NOTED.
  
 DUE TO THE REVISED PLAN THE FOLLOWING COMMENTS ARE
 REQUIRED FOR CODE COMPLIANCE.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A)(1). THE ONE ON THE PLAN IS INSIDE, THE
 PURPOSE OF THIS ARTICLE IS TO DISCONNECT THE SERVICE
 CONDUCTORS OUTSIDE TJHE BUILDING.
 .
 2} CRCUIT # 13, SMALL APPLIANCE IS NOW IN THE FOYER AS
 WELL AS THE KITCHEN STILL IN VIOLATION OF
 210.52(B)(2).
  
 3} CLARIFY THE CLOUD WITH 54" MARKED AT ALL CEILING
 FANS. SEE 110.3(B) INSTALLATION AND USE LISTED OR
 LABELED EQUIPMENT SHALL BE INSTALLED AND USED IN
 ACCORDANCE WITH ANY INSTRUCTIONS INCLUDED IN THE
 LISTING OR LABELING.
  
 4} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.THE REAR RECEPTALE IS MISSING ON THE PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718