2008-08-27 11:44:30 | 2004 FBC W/2007 REVISIONS |
| LEVEL 3 ALTERATION AND ADDITION |
| EXPIRED PERMIT 05070071 |
| |
| DENIED BY BUILDING |
| |
| 1) THE RAS 117 CALCULATIONS HAVE INCORRECT INFORMATION |
| LISTED FOR THE FASTENING DATA FROM THE NOA. THE NOA |
| FASTENER SPACING IS 8" OC IN 4 ROWS, ONE OF WHICH IS |
| THE LAP. THE NUMBER OF ROWS IN THE FIELD IS 3, WHICH |
| DOES NOT INCLUDE THE LAP. THE ROW SPACING IS 9.34". |
| HOWEVER, THE CALCULATED FASTENER SPACINGS ARE |
| ACCEPTABLE. PLEASE REVISE THE RAS CALCULATIONS TO |
| CONCUR WITH THE NOA. NOTE: THE SYSTEM THAT WAS SELECTED |
| REQUIRES SCREWS AND 3" PLATES FOR FASTENERS. FAC RULE |
| 9B-72 |
| |
| 2) THE PRODUCT APPROVAL FOR THE TOWN AND COUNTRY STORM |
| PANELS HAS NO REQUIREMENT FOR GLASS SEPARATION PROVIDED |
| THE MINIMUM PANEL LENGTHS ARE AS NOTED IN TABLE 2 ON |
| SHEET 6. USING DIRECT MOUNT WITH PANELMATE ANCHORS THE |
| MINIMUM LENGTH IS 52". THERE ARE 2 OPENINGS WITH SPANS |
| OF 46" THAT DO NOT COMPLY. PLEASE CORRECT. SEE TABLE 2 |
| OF PRODUCT APPROVAL. NOT: THE DRAWINGS THAT WERE |
| SUBMITTED WERE PARTIALLY ILLEGIBLE AND HAVE BEEN |
| REPLACED WITH NEW PAGES. R301.2.1.2 |
| |
| 3) ON THE STORM PANEL SCHEDULE UNDER SHUTTER MOUNT |
| CONNECTION SECTION 8 IS SPECIFIED. NUMBER 8 ON SHEET 1 |
| IS FOR "F" TRACK. PANELMATES ARE USED FOR DIRECT MOUNT. |
| PLEASE CLARIFY. ALSO INDICATE CONNECTION TYPE AS C1, |
| C2, C3 OR C4, WHICH IS NEEDED TO DETERMINE FASTENER |
| SPACING FROM THE TABLES ON SHEETS 5 AND 6 OF THE |
| PRODUCT APPROVAL. SEE SHEETS 2 AND 3 OF PRODUCT |
| APPROVAL.R301.2.1.2 |
| |
| 4) SUBMIT 2 COPIES OF PRODUCT APPROVALS APPROVED BY THE |
| DESIGNER OF RECORD FOR WINDOW MULLIONS THAT WILL USED |
| ON LIVING ROOM WINDOW. FAC RULE 9B-72 AND FBC 106.3.3* |
| CITY AMENDMENTS |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |