2008-12-31 09:19:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| NOTE: PLEASE HAVE LICENSED PLUMBING CONTRACTOR APPLY |
| FOR PERMIT. PLEASE NOTE THAT THE VALUATION OF THIS |
| PROJECT WILL BE INCREASED DUE TO THE NEW PLUMBING. |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED TO MEET CODE |
| COMPLIANCE. |
| |
| 1. SHEET P-1 SANITARY RISER DIAGRAM: THE KITCHEN SINK |
| SHALL DRAIN DOWNSTREAM OF THE WET VENTED BATHROOMS. PER |
| 909.1 WET VENT PERMITTED. |
| |
| 2. SHEET P-1 SANITARY RISER DIAGRAM. THE WASHER IS |
| SIZED WRONG, PLEASE CORRECT THE FOLLOWING. |
| (A) 406.3 WASTE CONNECTION. THE AUTOMATIC CLOTHES |
| WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH DRAIN OR |
| DRAINAGE STACK OF 3 INCHES IN DIAMETER. |
| |
| (B) 708.3.4 BASE OF STACK. A CLEANOUT SHALL BE PROVIDED |
| AT THE BASES OF EACH WASTE OR SOIL STACK. |
| |
| (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL |
| CLEANOUTS (CLEANOUT FOR WASHING MACHINE SHALL BE |
| LOCATED AT 4' A.F.F.) |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| END OF COMMENTS: |
| |
| *IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |