Plan Review Notes For Permit 08020371 |
Permit Number |
08020371 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-06-16 13:21:08 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | CYCLES: | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 | | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | 1} THE ELECTRIC METER LOCATIONS ON SHEET A-1AND E-1 ARE | | DIFFERENT. CORRELATE SAME.A-1 INDICATES A NEW SERVICE | | AND E-1 INDICATES EXISTING SERVICE. | | | | 2} THE RISER DIAGRAM ON SHEET E-1 RATES THE PANEL AND | | DISCONNECT AT 150 AMPS. THE PANEL SCHEDULE INDICATES | | 200 AMP MAIN BREAKER, CORRELATE SAME TO SHOW ACTUAL | | INTENTION. | | | | 3} THE RISER DIAGRAM SHOWS A 150 AMP DISCONNECT, NONE | | IS LOCATED ON THE PLAN. | | | | 4} ALL DEVICES ARE LABLED WITH CIRCUIT NUMBERS EXCEPT | | THE DINING ROOM. SEE 210.52(B)(1) FOR SMALL APPLIANCE | | REQUIREMENTS. | | | | 5} CIRCUIT #13, SMALL APPLIANCE, IN THE HALLWAY IS IN | | VIOLATION OF 210.52(B)(1). | | | | 6} SEE 210.52(E) FOR RECEPTACLE REQUIREMENTS OUTDOORS, | | THERE IS NONE IN THE FRONT. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|