Plan Review Notes For Permit 08020371
Permit Number 08020371
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-16 13:21:08 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1
 AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE ELECTRIC METER LOCATIONS ON SHEET A-1AND E-1 ARE
 DIFFERENT. CORRELATE SAME.A-1 INDICATES A NEW SERVICE
 AND E-1 INDICATES EXISTING SERVICE.
  
 2} THE RISER DIAGRAM ON SHEET E-1 RATES THE PANEL AND
 DISCONNECT AT 150 AMPS. THE PANEL SCHEDULE INDICATES
 200 AMP MAIN BREAKER, CORRELATE SAME TO SHOW ACTUAL
 INTENTION.
  
 3} THE RISER DIAGRAM SHOWS A 150 AMP DISCONNECT, NONE
 IS LOCATED ON THE PLAN.
  
 4} ALL DEVICES ARE LABLED WITH CIRCUIT NUMBERS EXCEPT
 THE DINING ROOM. SEE 210.52(B)(1) FOR SMALL APPLIANCE
 REQUIREMENTS.
  
 5} CIRCUIT #13, SMALL APPLIANCE, IN THE HALLWAY IS IN
 VIOLATION OF 210.52(B)(1).
  
 6} SEE 210.52(E) FOR RECEPTACLE REQUIREMENTS OUTDOORS,
 THERE IS NONE IN THE FRONT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718