Plan Review Notes
Plan Review Notes For Permit 08020371
Permit Number 08020371
Review Stop B
Sequence Number 2
Notes
Date Text
2008-06-24 16:25:302004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATION AND ADDITION
 EXPIRED PERMIT 05070071
  
 DENIED BY BUILDING
  
 1) THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE OF THE ARCHITECT. COPIED SIGNATURES ARE NOT
 ACCEPTABLE. THE DATE SEAL IS AFFIXED IS ALSO REQUIRED.
 SEE FS 481 AND FAC 61G1-16.003. REPEAT COMMENT.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR GLAZED FRENCH DOORS AS REQUIRED BY FAC RULE
 9B-72. REPEAT COMMENT.
  
 3) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 CASEMENT WINDOWS IS EXPIRED AND DOES NOT CORRESPOND
 WITH THE NOA NUMBERS LISTED ON THE FLORIDA COVER SHEET.
 SUBMIT THE CORRECT NOA. RULE 9B-72
  
 4) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE PRODUCT APPROVAL FOR THE GAF MODIFIED ROOFING
 WILL BE USED. SPECIFY THE FASTENING OPTION AND DESIGN
 PRESSURE FOR THE ASSEMBLY. SUBMIT RAS 117 CALCULATIONS
 FOR ENHANCED FASTENING AS REQUIRED BY LIMITATION NUMBER
 7 OF THE PRODUCT APPROVAL. R905.11.3
  
 5) THE INSTALLATION SCHEDULE THAT WAS SUBMITTED FOR THE
 STORM PANELS IS FROM EASTERN METAL SUPPLIES AND THE
 PRODUCT APPROVALS ARE FROM TOWN AND COUNTRY. THE
 SUBSTRATE IS LISTED AS CONC. BLOCK AND THE PLANS SHOW
 WOOD FRAME AT SOME OF THE OPENINGS. PLEASE CORRECT. FBC
 R 301.2.1.2
  
 6) ON SHEET A-2 GENERAL NOTE SPECIFIES IMPACT RATED PGT
 DOORS. THE PRODUCT APPROVALS THAT WERE SUBMITTED ARE
 FOR IMPACT RATED WINDOWS AND PANEL DOORS. IF WINDOWS
 AND DOORS ARE IMPACT RATED, THEN STORM PANELS ARE NOT
 REQUIRED. PLEASE CLARIFY.
  
 7)THE ENERGY CALCULATIONS THAT WERE SUBMITTED ON FORM
 600A-04R ARE TAKING A CEILING FAN CREDIT. THE ELECTRIC
 PLANS DO NOT SPECIFY A CEILING FAN IN THE LIVING ROOM,
 WHICH IS REQUIRED IF TAKING THE CREDIT. ALSO, SPECIFY
 THE SIZE OF THE FANS ON THE PLANS.SEE FBC
 13-607.1.A.1
  
 8) SUBMIT BUCK DETAILS FOR THE WINDOWS AND DOORS. FBC
 R613.6.1.1 THE DOOR JAMB DETAIL THAT WAS SUBMITTED ON
 THE 8.5" X 11" SHEET, IS NOT SIGNED, SEALED AND DATED
 BY THE DESIGNER OF RECORD, IT DOES NOT HAVE A TITLE
 BLOCK IDENTIFYING THE PROJECT AND IT REFERS TO DETAIL 5
 ON S7 WHICH WAS NOT SUBMITTED AS PART OF THE DOCUMENTS
 FOR THIS PROJECT. SEE FAC 61G1-16.003.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]