Date |
Text |
2008-02-21 09:40:27 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, EXISTING BUILDING |
| CODE 2004,2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE ARCHITECT'S SIGNATURE AND SEAL IS A PHOTOCOPY. |
| WHEN SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE |
| WET AND THE SEAL MUST MAKE AN IMPRESSION PER |
| 481.221(1)(A) FLORIDA STATUTES.2} |
| |
| 2} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| PLAN. |
| |
| 3.} SUBMIT A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS, |
| PANEL SCHEDULESPER 106.3.5.4 FBC. PER 215.5 NEC. |
| |
| 4} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN |
| INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A |
| PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE |
| ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL |
| DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS |
| LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS |
| SHALL BE INTERCONNECTED AND HARD WIRED. SEE ARTICLE FOR |
| EXCEPTIONS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |