Plan Review Notes
Plan Review Notes For Permit 08020322
Permit Number 08020322
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-15 12:26:12*** DENIEDREVIEW***
  
 1) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING
 RELEVANT CODES.
 PLEASE SEE CODE STATED ON PLANS FOR 2006 NFPA-101 AND
 2007 NFPA-72IS NOT YET ADOPTED BY THE STATE.
 PLANS SHOULD REFLECT.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 FBC 106.1.2, 106.3.5.1.2, 106.5
 FS 553.73
 FBC CHAPTER 35 FOR REFERENCE STANDARDS.
  
 2) NOTE: PLEASE SEE PLANS ARE NOT SIGNED WITH SIGNATURE
 AS ON FILE WITH THE CITY OF WEST PALM BEACH.
 PLEASE ADJUST AS PER FS 471.025/ FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE SUBMITTED PERMIT APPLICATION IS FOR
 WORK IN SUITE #802 YET THE PLANS SHOWS A NEW
 DISCONNECT, TRANSFORMER AND PANEL FOR A SUITE #803.
 PLEASE CLARIFY WHERE THE SCOPE OF WORK IS BEING DONE
 AND COORDINATE PLANS.
 FBC 106.1.2 COORDINATION
  
 4) NOTE: PLEASE SEE THAT THE CIRCUITING ON PANEL
 SCHEDULES FOR NEW ARE TO BE SPECIFIC TO ROOMS AND AREAS
 IN WHICH THE FEED.
 FOR EXAMPLE> OFFICE RECEPTS 102, ETC
 408.4, FBC 106.1.2, 106.5
  
 5) NOTE: PLEASE CLARIFY NEW OR EXISTING LIGHTING
 CONTROLS BEING INSTALLED. PLEAS KNOW IF ANY OF THESE
 ARE NEW THEY ARE REQUIRED TO MEET FBC 13-415.1.ABC.1.1,
 .1.2, .1.3.
 FBC 13-101. PLEASE KNOW AT THIS TIME DETERMINATION OF
 ACTUAL SCOPE IS NOT CLEAR.
  
 6) NOTE:PLEASE BE SURE TO INCLUDE EAST TOWER ON
 PLANS. ON ANY SHEETS WHICH DO NOT NEED TO RE-PRINTED
 THIS CAN BE ADDED BY HAND.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  