2008-02-15 12:26:12 | *** DENIEDREVIEW*** |
| |
| 1) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING |
| RELEVANT CODES. |
| PLEASE SEE CODE STATED ON PLANS FOR 2006 NFPA-101 AND |
| 2007 NFPA-72IS NOT YET ADOPTED BY THE STATE. |
| PLANS SHOULD REFLECT. |
| 2004 FBC W/ 2007 REVISIONS. |
| 2005 NFPA-70 |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| FBC 106.1.2, 106.3.5.1.2, 106.5 |
| FS 553.73 |
| FBC CHAPTER 35 FOR REFERENCE STANDARDS. |
| |
| 2) NOTE: PLEASE SEE PLANS ARE NOT SIGNED WITH SIGNATURE |
| AS ON FILE WITH THE CITY OF WEST PALM BEACH. |
| PLEASE ADJUST AS PER FS 471.025/ FAC 61G15-23.002 |
| |
| 3) NOTE: PLEASE SEE SUBMITTED PERMIT APPLICATION IS FOR |
| WORK IN SUITE #802 YET THE PLANS SHOWS A NEW |
| DISCONNECT, TRANSFORMER AND PANEL FOR A SUITE #803. |
| PLEASE CLARIFY WHERE THE SCOPE OF WORK IS BEING DONE |
| AND COORDINATE PLANS. |
| FBC 106.1.2 COORDINATION |
| |
| 4) NOTE: PLEASE SEE THAT THE CIRCUITING ON PANEL |
| SCHEDULES FOR NEW ARE TO BE SPECIFIC TO ROOMS AND AREAS |
| IN WHICH THE FEED. |
| FOR EXAMPLE> OFFICE RECEPTS 102, ETC |
| 408.4, FBC 106.1.2, 106.5 |
| |
| 5) NOTE: PLEASE CLARIFY NEW OR EXISTING LIGHTING |
| CONTROLS BEING INSTALLED. PLEAS KNOW IF ANY OF THESE |
| ARE NEW THEY ARE REQUIRED TO MEET FBC 13-415.1.ABC.1.1, |
| .1.2, .1.3. |
| FBC 13-101. PLEASE KNOW AT THIS TIME DETERMINATION OF |
| ACTUAL SCOPE IS NOT CLEAR. |
| |
| 6) NOTE:PLEASE BE SURE TO INCLUDE EAST TOWER ON |
| PLANS. ON ANY SHEETS WHICH DO NOT NEED TO RE-PRINTED |
| THIS CAN BE ADDED BY HAND. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |