Plan Review Notes
Plan Review Notes For Permit 08020280
Permit Number 08020280
Review Stop E
Sequence Number 2
Notes
Date Text
2008-10-08 12:22:51** DENIED **
  
  
 ** PLANS NOW SUBMITTED HAVE BEEN REVISED. PLEASE SEE
 THE FOLLOWING COMMENTS
  
 1) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM IS
 NOT COMPLETE. PLEASE SEE 250.50,250.56 ETC. NO GROUND
 RODS OR OTHER SYSTEM SHOWN. ONLY NOTED FOR CWP.
  
 2) NOTE: PLEASE INDICATE THE CONDUCTORS FROM NEW GUTTER
 TO MAINS.
 310.16, 240.4.
  
 3) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR NEW
 MAINS/SERVICE EQUIPMENT. 110.03
 FBC 106.1.1
  
 4) NOTE: PLEASE CLARIFY THE LIGHTING CONTROLS AS NOTED
 AND SHOWN ON PLANS. SOME PARTS OF THE PLANS INDICATE
 OCCUPANCY DEVICES HOWEVER NOT IN ALL LOCATIONS.
 PLEASE SEE FBC 13-415.1.ABC.1.2 FOR CONTROLS IN
 SEPARATE SPACES.
  
 5) NOTE: PLEASE SEE FBC 108.3, AS SCOPE OF WORK HAS
 INCREASED PLEASE REVISED VALUE ON PERMIT APPLICATION.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  