2008-02-15 17:42:28*** DENIEDREVIEW***
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES SHALL
 BE STATED ON PLANS RELEVANT FOR SCOPE OF WORK.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE THE PLANS NEED TO SHOW HOW AND
 WHERE INTERIOR LIGHTING IS BEING FED, CONTROLLED ETC.
 PLEASE SEE NOTES FROM FIRE MARSHAL ALSO AS MINIMUM
 LIGHTING FOR EMERGENCY ILLUMINATION OF SOME SORT WILL
 BE REQUIRED PER LS 7.8 AND 7.9.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING.
 PLEASE VERIFY AND STATE ON PLANS IF THERE ARE ANY OTHER
 EXISTING LIGHTING FIXTURES WHICH MAY BE ENERGIZED OR
 LOCATED AT PROPERTY.
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE FOR
 EXTERIOR PER 13-415.2, 13-415.2.ABC.1.3.
 PLEASE BE SURE TO INCLUDE FIXTURE SCHEDULE FOR NEW
 FIXTURES.
  
 4) NOTE: PLEASE SEE 13-415.1.ABC.1.4 FOR CONTROL OF
 EXTERIOR LIGHTING.
  
 5) NOTE: PLEASE SUBMIT PANEL SCHEDULE(S) FOR NEW
 LIGHTING BEING SHOWN ON PLANS. PLEASE COMPLETE THE
 CIRCUITS ON PLANS. BRANCH CIRCUIT(S), SIZE OF OVER
 CURRENT PROTECTION, CONDUCTOR SIZES ETC.
 240.4, 310.16, 408.4 ETC
 FBC 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE LOCATION OF THE SERVICE IS IN
 QUESTION AS THE SERVICE DROP APPEARS TO NOT MEET 230
 PART I OR PART II. THERE IS NOT ENOUGH INFORMATION.
 PLEASE SEE RISER WHICH ONLY SHOWS A BOX WHICH STATES
 400A SINGLE PHASE. WHAT IS THIS? THIS CAN BE ASSUMED
 THIS IS A METER HOWEVER PLANS NEED TO BE SPECIFIC FOR
 ALL ELECTRICAL EQUIPMENT.
  
 7) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AND
 FEEDERS ARE NOT RATED FOR THE 150AMP MAINS OR PANELS
 PER 310.16.
 ** THIS IS NOT A RESIDENCE AND 310.15B6 MAY NOT BE
 USED.
 240.4, 310.16.
  
 8) NOTE: PLEASE SEE 250.6 AND 250.24 AS *EQUIPMENT
 GROUNDING CONDUCTORS* ARE NOT PERMITTED AHEAD OF THE
 FIRST MEANS OF DISCONNECT.
  
 9) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY
 DESIGN PROFESSIONAL. PLEASE SEE FBC 105.3.1.2, FS
 481.229, 471.003, 489.
  
 10) NOTE: PLEASE SEE PANEL *A* MAY NOT BE LOCATED IN
 CLOSET AS SHOWN.
 PLEASE SEE110.26, 240.24, 408.17
  
 11) NOTE: PLEASE SUBMIT THE AIC RATINGS PER 110.9.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE MISSING COLD WATER PIPE REQUIRED
 TO BE PART OF THE GROUNDING ELECTRODE SYSTEM.
 250.50
  
 13) NOTE: PLEASE CLARIFY THE CONDUITS SHOWN ON RISER.
 WHAT IS CMT OR EMC?
 110.3, NEC 300, 320-388
  
 14) NOTE: PLEASE PROVIDE INFORMATION ON PLANS IF THIS
 IS A SHELL BUILDING AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2, 110
  
 15) NOTE: PLEASE KNOW THERE IS CURRENTLY A HOLD IN
 SYSTEM FOR EXPIRED PERMITS AT THIS LOCATION PER THE
 CHIEF BUILDING INSPECTOR.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II