2008-02-21 12:17:18 | 2004 FBC W/2007 REVISIONS | | INSTALL GENERATOR | | | | DENIED BY BUILDING | | | | 1)NO PERMIT PERTAINING TO A GENERATOR | | SHALL BE ISSUED UNTIL AN APPLICATION FOR | | THE GENERATOR, WITH A REVIEW FOR THE | | GENERATOR, BY BUILDING, ELECTRIC, | | MECHANICAL, AND ZONING PLAN REVIEWERS. | | THE BUILDING REVIEW WILL BE FOR SLAB AND ANCHORING, | | (SUBMIT A DETAIL) SEE FBC 1609.1.3, ELECTRICAL | | REVIEW WILL BE FOR THE TRANSFER SWITCH, | | (SUBMIT MANUF. SPECIFICATION SHEETS - | | MUST BE LISTED AND APPROVED), MECHANICAL | | REVIEW FOR THE EXHAUST, (PROVER | | CLEARANCES FROM OPENINGS IN HOUSES | | INCLUDING ADJOINING IF APPLICABLE), AND | | ZONING, (SHOWING DISTANCE FROM PROPERTY | | LINE ECT. - SURVEY REQUIRED). | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | |
|