Plan Review Notes For Permit 08020236 |
Permit Number |
08020236 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-05-19 08:37:07 | REDLINED THE FOLLOWING ITEMS ON PLANS. | | | | | | 1) THE LIGHTING POWERE DENSITIES PER 13-415.2 ARE | | ATTACHED TO LIGHTING SHEETS. | | | | 2) THE DESIGNATION OF THE IT ROOM WAS CHANGED TO A | | COMMUNICATIONS ROOM. NO WIRING METHODS ALLOWED IN NEC | | 645 ARE PERMITTED TO BE USED. MUST COMPLY WITH ALL | | WIRING METHODS OF NEC CHAPTERS 1-4. | | WIRING METHODS OF 645 ARE ONLY PERMITTED WHEN A TRUE IT | | ROOM MEETING ALL ITEMS AS LISTED IN 645.2. | | IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS | | OFFICE. | | | | DEWEY PALMER | | ELECTRICLA PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH |
|