Plan Review Notes
Plan Review Notes For Permit 08020236
Permit Number 08020236
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-19 08:37:07REDLINED THE FOLLOWING ITEMS ON PLANS.
  
  
 1) THE LIGHTING POWERE DENSITIES PER 13-415.2 ARE
 ATTACHED TO LIGHTING SHEETS.
  
 2) THE DESIGNATION OF THE IT ROOM WAS CHANGED TO A
 COMMUNICATIONS ROOM. NO WIRING METHODS ALLOWED IN NEC
 645 ARE PERMITTED TO BE USED. MUST COMPLY WITH ALL
 WIRING METHODS OF NEC CHAPTERS 1-4.
 WIRING METHODS OF 645 ARE ONLY PERMITTED WHEN A TRUE IT
 ROOM MEETING ALL ITEMS AS LISTED IN 645.2.
 IF THERE ARE ANY QUESTIONS, PLEASE CONTACT THIS
 OFFICE.
  
 DEWEY PALMER
 ELECTRICLA PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH