Plan Review Notes For Permit 08020236 |
Permit Number |
08020236 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-03-19 08:47:26 | DENIED; | | 1. ROOM 272 PRIVATE BATHROOM IS REQUIRED TO BE | | ADAPTABLE PER FBC BUILDING CHAPTER 11 SECTION | | 11-4.1.3(11). SHOW DETAIL WITH WIDTH AND LENGTH | | MEASUREMENTS. W/C TO BE 18" OFF WALL AND SHOW TURNING | | RADIUS. | | 2. STAFF BATHROOM # 275 NOT TO ACCESSIBILITY CODE | | SECTION 11-4.1.2. | | (A) DOOR SWINGS INTO THE CLEAR FLOOR SPACE OF | | THE LAVATORY. SECTION 11-4.22.2(1). | | (B) TURNING RADIUS IN BATHROOM REQUIRED, SEE | | SECTION 11-4.22.3. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|