2008-02-11 15:32:25 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED: |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION *401.1 SCOPE. |
| **THE SUBMITTED ISOMETRIC IS NOT INDICATING THE |
| CORRESPONDING LENGTHS TO ALL CUT SECTIONS OF PIPE ON |
| THE PROPOSED POOL HEATER. REFERENCE THE RED CIRCLED |
| AREAS HIGH LIGHTED YELLOW INDICATING THIS. |
| |
| 2. AT A MINIMUM GAS PLANS SHALL REFLECT THE PERMIT |
| APPLICATION. THE PERMIT APPLICATION HAS DELETED THE |
| GENERATOR. PLEASE CORRELATE THE PLANS WITH THE PERMIT |
| APPLICATION AND DELETE THE PIPING AND FITTINGS TO THE |
| GENERATOR. PER FBC-2004 FUEL GAS, SECTION *401.1 |
| SCOPE. |
| |
| 3. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| |
| ********IMPORTANT INFORMATION******** |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| EXAMINER FOR REFERENCE FOR THE |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |