Plan Review Notes For Permit 08020201 |
Permit Number |
08020201 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-04-24 09:48:12 | 2004 FBC W/2007 REVISIONS | | REVISION TO INSTALL PIPE STANDS ON NEW ROOF | | | | DENIED BY BUILDING | | | | 1) THE CODE AND ASCE 7 EDITIONS SPECIFIED ON THE | | ENGINEER'S DRAWINGS ARE INCORRECT. PLEASE UPDATE. SEE | | 2004 FBC AND ASCE7-02. | | | | 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND | | INSTALLATION INSTRUCTIONS FOR THE EPOXY THAT WILL BE | | USED TO ATTACH THE PAVERS TO THE ROOF COVERING. FBC | | 106.1.2* CITY AMENDMENTS. | | | | 3) SPECIFY HOW THE TWO CONCRETE PAVERS WILL BE ANCHORED | | TOGETHER. FBC 106.1.1* CITY AMENDMENTS. | | | | 4) SPECIFY THE LENGTH OF THE FOUR 3/8" DIAMETER TAP CON | | ANCHORS.FBC 106.1.1* CITY AMENDMENTS. | | | | 5) PLEASE CLARIFY HOW THE JOHNS MANVILLE CAP SHEET | | ADHERED WITH ROOFING CEMENT TO WHICH THE PAVERS AND | | STANDS ARE ATTACHED WILL RESIST WIND-INDUCED | | OVERTURNING, UPLIFT AND SLIDING AND PROVIDE A | | CONTINUOUS LOAD PATH AS REQUIRED BY 2004 FBC 1609.1.3. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|