Plan Review Notes
Plan Review Notes For Permit 08020201
Permit Number 08020201
Review Stop B
Sequence Number 3
Notes
Date Text
2008-04-24 09:48:122004 FBC W/2007 REVISIONS
 REVISION TO INSTALL PIPE STANDS ON NEW ROOF
  
 DENIED BY BUILDING
  
 1) THE CODE AND ASCE 7 EDITIONS SPECIFIED ON THE
 ENGINEER'S DRAWINGS ARE INCORRECT. PLEASE UPDATE. SEE
 2004 FBC AND ASCE7-02.
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE EPOXY THAT WILL BE
 USED TO ATTACH THE PAVERS TO THE ROOF COVERING. FBC
 106.1.2* CITY AMENDMENTS.
  
 3) SPECIFY HOW THE TWO CONCRETE PAVERS WILL BE ANCHORED
 TOGETHER. FBC 106.1.1* CITY AMENDMENTS.
  
 4) SPECIFY THE LENGTH OF THE FOUR 3/8" DIAMETER TAP CON
 ANCHORS.FBC 106.1.1* CITY AMENDMENTS.
  
 5) PLEASE CLARIFY HOW THE JOHNS MANVILLE CAP SHEET
 ADHERED WITH ROOFING CEMENT TO WHICH THE PAVERS AND
 STANDS ARE ATTACHED WILL RESIST WIND-INDUCED
 OVERTURNING, UPLIFT AND SLIDING AND PROVIDE A
 CONTINUOUS LOAD PATH AS REQUIRED BY 2004 FBC 1609.1.3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW