Plan Review Notes
Plan Review Notes For Permit 08020194
Permit Number 08020194
Review Stop G
Sequence Number 1
Notes
Date Text
2008-02-11 08:27:39****************PROVISO****************
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
 ****************PROVISO****************
 PER FBC MECHANICAL SECTION 303.4 PROTECTION FROM
 DAMAGE. APPLIANCES (WATER HEATER IN GARAGE) SHALL NOT
 BE INSTALLED IN A LOCATION WHERE SUBJECT TO MECHANICAL
 DAMAGE UNLESS PROTECTED BY APPROVED BARRIERS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]