2009-02-23 14:22:44 | ** DENIED AUDIT ** | | | | | | | | 1) NOTE: THERE IS STILL NO REVISED LIGHTING PERFORMANCE | | CALCULATIONS SUBMITTED. THERE HAS BEEN AN INCREASE IN | | WATTAGE FROM THE ORIGINAL CALCULATIONS. | | SOME FIXTURES HAVE BEEN REVISED TO ACTUALLY DOUBLE THE | | WATTAGE FROM THE ORIGINAL FIXTURE DESIGNS. | | PLEASE SEE 13-415.2.ABC.1.1,.1.2, 13-415.2.B.2. | | PLEASE BE SURE TO ALSO SUBMIT THE LATEST REVISED | | FIXTURE LEGEND. THE PREVIOUS PLANS WHICH CONTAINED THE | | REVISED FIXTURE LEGEND WERE REJECTED ON THE PREVIOUS | | REVIEW DATED 10/31/2008. | | NO REVISED PLANS ADDRESSING THIS ISSUE HAVE BEEN | | SUBMITTED SINCE THAT DATE. | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | CONTACT THIS REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|