Plan Review Notes
Plan Review Notes For Permit 08020160
Permit Number 08020160
Review Stop E
Sequence Number 7
Notes
Date Text
2009-02-23 14:22:44** DENIED AUDIT **
  
  
  
 1) NOTE: THERE IS STILL NO REVISED LIGHTING PERFORMANCE
 CALCULATIONS SUBMITTED. THERE HAS BEEN AN INCREASE IN
 WATTAGE FROM THE ORIGINAL CALCULATIONS.
 SOME FIXTURES HAVE BEEN REVISED TO ACTUALLY DOUBLE THE
 WATTAGE FROM THE ORIGINAL FIXTURE DESIGNS.
 PLEASE SEE 13-415.2.ABC.1.1,.1.2, 13-415.2.B.2.
 PLEASE BE SURE TO ALSO SUBMIT THE LATEST REVISED
 FIXTURE LEGEND. THE PREVIOUS PLANS WHICH CONTAINED THE
 REVISED FIXTURE LEGEND WERE REJECTED ON THE PREVIOUS
 REVIEW DATED 10/31/2008.
 NO REVISED PLANS ADDRESSING THIS ISSUE HAVE BEEN
 SUBMITTED SINCE THAT DATE.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  