| ** DENIED REVISION** |
| |
| 1) NOTE: PLEASE SHOW AND DISPLAY ALL REVISIONS AS NOTED |
| ON TITLE BLOCKS. FOR EXAMPLE THE LAST REVISION ON |
| RECORD TO DATE FOR SHEET E500 IS REVISION #4, WHEREAS |
| THE NEW REVISED SHEET CONTAINS REVISION #6. WHERE IS |
| REVISION #5 LOCATED ON PLANS? NO CLOUDS OR TRIANGLES |
| ARE SHOWN INDICATING THESE REVISIONS. THERE WAS A |
| PREVIOUS REV #5 HOWEVER FOR OTHER SHEETS. |
| PLEASE COORDINATE PLANS. |
| FBC 106.1.1 |
| FBC CHAPTER 13, NEC 220 |
| |
| 2) NOTE: PLEASE SUBMIT REVISED LIGHTING PERFORMANCE |
| CALCULATIONS. AS THE FIXTURES HAVE BEEN REVISED TO |
| INCREASE WATTAGES THE PREVIOUSLY SUBMITTED CALCULATIONS |
| NO LONGER COORDINATE. |
| PLEASE SEE 13-415.2,13-415.2.ABC.1.1,.1.2. |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| |